Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0723-01773
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2023 Commercial Mechanical APPROVED
08/23/2023 Commercial Plumbing APPROVED
08/23/2023 Commercial Structural APPROVED
07/24/2023 Site Zoning APPROVED
08/23/2023 Water - PDSD APPROVED
07/25/2023 Site Engineering NOT REQUIRED
08/23/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/16/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The wording is not legible, especially if trying to enlargr to read. Please resubmit plans using a legible PDF format.

2 Provide Tamper Resistant and combination type Arc Fault protection for the new 120 volt receptacles, per NEC 210.12, 406.12.

Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
07/24/2023 Fire New Construction REVIEW COMPLETED
07/21/2023 PDSD Application Completeness REVIEW COMPLETED It appears the description of work lists multiple buildings/units. Each individual building/unit requires its own permit. This permit is for (207 N MAGUIRE AV Unit:BLDG J UNIT 184) only, please start new permits for the other buildings/units.