Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0723-01773
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/23/2023 | Commercial Mechanical | APPROVED | |||
08/23/2023 | Commercial Plumbing | APPROVED | |||
08/23/2023 | Commercial Structural | APPROVED | |||
07/24/2023 | Site Zoning | APPROVED | |||
08/23/2023 | Water - PDSD | APPROVED | |||
07/25/2023 | Site Engineering | NOT REQUIRED | |||
08/23/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/16/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The wording is not legible, especially if trying to enlargr to read. Please resubmit plans using a legible PDF format. 2 Provide Tamper Resistant and combination type Arc Fault protection for the new 120 volt receptacles, per NEC 210.12, 406.12. Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
||
07/24/2023 | Fire New Construction | REVIEW COMPLETED | |||
07/21/2023 | PDSD Application Completeness | REVIEW COMPLETED | It appears the description of work lists multiple buildings/units. Each individual building/unit requires its own permit. This permit is for (207 N MAGUIRE AV Unit:BLDG J UNIT 184) only, please start new permits for the other buildings/units. |