Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0723-01706
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2023 | Site Engineering | NOT REQUIRED | |||
| 02/28/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/14/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. The ventilation rate for marijuana grow facilities with enhanced carbon dioxide levels are not represented in Table 403.3.1.1, IMC 2018. Provide an engineering evaluation of the minimum ventilation rate for the facility. Reference: Section 403.3.1.1, IMC 2018. 2. The 19 heat pumps serving the facility are equipped with activated carbon filters to mitigate the plant odor. Provide a maintenance protocol and schedule to ensure that the activated carbon filters continue to reduce the odors to acceptable levels. Reference: Section 107.2.1, IBC 2018. |
||
| 02/28/2024 | External Reviewers - Stantec | REQUIRES RESUBMIT | Project under building review by Stantec, submittal of approved Stantec construction documents required. Please contact Doris.Benoit@tucsonaz.gov for additional information. | ||
| 08/04/2023 | Fire New Construction | REQUIRES RESUBMIT | -Include CO2 gas detection alarm in your deferred submittals, sheet X0.0 -Gas detection alarm shall comply with IFC 5307.4.3. Mechanical shall comply with 5307.4.4 (1 cfm per square foot, exhaust duct 12" AFF in grow rooms and activation of mechanical exhaust by gas detection alarm). john.vincent@tucsonaz.gov 5203495581 |
||
| 07/31/2023 | Site Zoning | REQUIRES RESUBMIT | CDRC Transmittal FROM: Loran Shamis, MBA; Lead Planner PDSD Zoning Review Section PROJECT: TC-COM-0723-01706 – Off-Site Marijuana Dispensary Cultivation Location Tenant Improvement (1st review) 4850 S Park Av TRANSMITTAL DATE: July 31, 2023 DUE DATE: August 13, 2023 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. The site is zoned I-1 and the proposed use is retail – off-site marijuana dispensary cultivation location which is a permitted use subject to use specific standards 4.9.9.E.2 and 4.9.13.Q (UDC, Table 4.8-5) 01. COMMENT: Demonstrate compliance with UDC 4.9.9.E.2.k.2 – An odor mitigation plan shall be submitted demonstrating compliance with odor control requirements. Zoning with review this plan in collaboration with Commercial Mechanical. For questions regarding Zoning comments, please contact me at: Loran.Shamis@tucsonaz.gov |
||
| 07/14/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |