Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0723-01631
Parcel: 124050590

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0723-01631
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2023 Commercial Mechanical APPROVED
08/03/2023 Commercial Plumbing APPROVED
07/11/2023 Site Zoning APPROVED
07/10/2023 Site Engineering NOT REQUIRED
08/09/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/02/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Ref; Power and Lighting plans.

1 Please indicate that the emergency light fixtures or the emergency part of the fixture must connect to an unswitched lighting circuit per NEC art 700.16.

2 Indicate the designated branch circuits and panels for the new receptacles and correlate with the panel schedules. NEC 408.4.

Ref; 2018 IBC section 107.2.1, 2017 NEC.
08/09/2023 Commercial Structural REQUIRES RESUBMIT Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. 402.4.2.1 & 708 IBC DEMISING WALL BETWEEN TWO SPACES, WALL MUST GO TO THE UNDERSIDE OF THE ABOVE FLOOR STRUCTURE WITH THE PROPER FIRE-RESISTANCE RATING. Please make this correction on Detail 1/A2.0
2. Each Unit must have their own building permit. NOTE: This permit will be used for Unit #980 (unit 978 will be crossed out from this set of drawings). Please apply for another permit on Unit #978.
3. As a Mercantile space Unit #980, what will be the type of business and product that will be offered for sale?
4. Please re-confirm that there are no fire sprinkler in this entire 3 story building.
5. Is there a fire alarm system. Please confirm this as well.
6. Is there lighted exit signs.
7. Is there the sign, "THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS IN USE" installed? Pleas locate on the drawings.
8. Valuation is on the low end at $5,000. Please provide the actual cost of material and labor for this project.
9. Please re-submit.
07/26/2023 Fire New Construction REVIEW COMPLETED
07/05/2023 PDSD Application Completeness REVIEW COMPLETED It appears the plan set submitted lists 2 addresses and each individual address requires its own permit. This permit is for 980 E University Bl only, please start a new permit for the other address.