Permit Number: TC-COM-0626-00937
Parcel: 14039041D

Address:
5451 E BENSON HY

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0626-00937
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2026 Site Engineering Standard APPROVED
07/13/2026 Site Zoning Standard APPROVED
07/15/2026 Commercial Building Standard NOT REQUIRED
07/15/2026 Commercial Mechanical Standard NOT REQUIRED
07/15/2026 Commercial Plumbing Standard NOT REQUIRED
07/15/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
07/15/2026 Water - PDSD Standard NOT REQUIRED
07/15/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/15/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0626-00937 (5451 E BENSON HY TUCSON, AZ 85756)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide an updated classification and zone drawing, NEC 500.4 & 514.3.
2. Show existing and new electrical wiring meets the requirements of NEC 514.4, and Parts II & III of NEC 501.
3. Show existing and new electrical complies with wiring methods as required in NEC 514.7, NEC 514.8, Sealing per 514.9, disconnects per 514.11.
4. Provide grounding and bonding of the new dispensers per NEC 514.16.
5. Provide updated electrical panel schedules and load calculations showing the additional fuel dispensers added.
6. Provide sheet C2, and detail 1, as called out for on sheet C1. Or correct the callout on C1, detail 1 to show the correct sheet/detail. Give each detail on Sheet C1 individual numbers.
07/15/2026 Fire New Construction Standard REVIEW COMPLETED Contact Inspector Jesus Silva for fire inspections and any additional requirements/information.
Jesus.Silva@tucsonaz.gov
5208377094
5204199177
06/24/2026 PDSD Application Completeness Express REVIEW COMPLETED