Permit Number: TC-COM-0626-00889
Parcel: 141148180

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0626-00889
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2026 Site Zoning APPROVED
07/02/2026 Water - PDSD APPROVED
06/18/2026 Site Engineering NOT REQUIRED
07/06/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/02/2026 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00889
ADDRESS/PARCEL: (9136 E VALENCIA RD Unit: UNIT 150 TUCSON, AZ 85747)
TC-COM-0526-00787 (3002 E GRANT RD Unit:UNIT 2 TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. RESULT OF RESEARCH WITHIN THE CITY OF TUCSON’S EXISTING BUILDING PERMIT RECORDS.
a. RESEARCH INDICATES THAT IN 2022, THE LAST LEGALLY PERMITTED BUSINESS within this space WAS A CLEANERS BUSINESS named Tucson Cleaners.
b. The floor plan of that Tucson Cleaners shows a very different configuration.
c. The submitted floor plan shows little resemblance to that last legally permitted space floor plan.
d. A COMPLETE SET OF DRAWINGS is required TO INCLUDE ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, ETC THAT ARE SEALED/SIGNED/DATED BY A LICENSED ARIZONA REGISTRANT.
2. DRINKING FOUNTAIN
a. Where the Building and Plumbing Codes require a drinking fountain, the City of Tucson will accept point of use water dispenser in lieu of the classically recognized drinking fountain.
b. The water dispenser must be listed and labeled in accordance with the Code.
c. The water dispenser must be connected to a permanent supply of potable water.
d. The water supply must be indicated on the plans and installed per code.
e. A clear floor space shall be provided for the cooler in compliance with chapter 6 of ICC A117.1.
f. A permanently mounted disposable cup dispenser shall be installed adjacent to the cooler with the dispensing end between 34" and 48" above finish floor and show the clear floor space complying to chapter 3 ICC A117.1 section 602.4.
g. NOTE: waste line shall also be necessary to be connected to this drinking fountainIn the Cover sheet list all the special inspections for this project.
3. The submitted valuation for the work done of $7,000 is not realistic. Either provide a construction estimate to include all the changes which includes all the interior walls (except for the restroom), the new mop sink, the washer/dryer, the new shower, the new mop sink, the reception desk along with the cash register, the new breakroom, the new refrigerator room, the relocation of the a/c diffusers & return grills, the relocation of the lights, the installation of the lighted exit sign with battery backup, the installation of emergency lights with battery backup, the installation of the water dispenser with direct connection to a water supply line/sewer waste line, relocating the fire sprinkler heads, etc.
4. OR we can use the valuation based on the International Building Code Valuation Table.
5. Should you wish to receive a copy of the Tucson Cleaners floor plan, please do let us know.
6. Please be aware that at the time of inspection, it may become necessary to open walls in order to conduct proper inspection. Please have someone at the site at the time who has the approval from the owner to open walls.
7. Please resubmit
06/24/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0626-00889 (9136 E VALENCIA RD Unit:UNIT 150 TUCSON, AZ 85747)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. Provide ‘as-built’ electrical and lighting plans showing compliance with Section 7-137(2) of the Tucson, Arizona Charter and General Ordinances, for electrical and lighting. https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az/0-0-0-5098

Additional comments may be forthcoming with complete electrical plans.
07/02/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00889
ADDRESS/PARCEL: 9136 E VALENCIA RD Unit:UNIT 150 TUCSON, AZ 85747

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. The plans indicate an existing clothes dryer, but there was no record of it back in 2022. Provide sufficient information to demonstrate that the existing dryer installation complies with the requirements of Section 504 of the 2024 IMC. Revise the plans as necessary. Reference: Section 504, IMC 2024.
07/02/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00889
ADDRESS/PARCEL: 9136 E VALENCIA RD Unit:UNIT 150 TUCSON, AZ 85747

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Provide ‘as-built’ plumbing plans. Also show compliance with Section 7-137 (5) & (11) of the Tucson, Arizona Charter and General Ordinances, for plumbing. https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az/0-0-0-5098.
06/21/2026 Fire New Construction REVIEW COMPLETED
06/18/2026 PDSD Application Completeness Express REVIEW COMPLETED