Permit Number: TC-COM-0626-00866
Parcel: 137055270

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0626-00866
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2026 Commercial Building Standard APPROVED
07/08/2026 Commercial Electrical Standard APPROVED
07/07/2026 Site Zoning Standard APPROVED Proposed signage shown on sheet A-3.1 will require a separate sign permit.
07/08/2026 Water - PDSD Standard APPROVED
07/08/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/18/2026 Site Engineering Standard NOT REQUIRED
07/08/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/08/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00866
ADDRESS/PARCEL: 5133 S CALLE SANTA CRUZ TUCSON, AZ 85706

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please show the size, routing, and termination of the condensate drains from the rooftop HVAC units. Reference: Section 307.2.1, IMC 2024 as amended by the City of Tucson.
07/08/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00866
ADDRESS/PARCEL: 5133 S CALLE SANTA CRUZ TUCSON, AZ 85706

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please ensure the shelf-mounted electric water heater detail on Sheet P-601 is consistent with the water isometric on Sheet P-102. For example, the detail shows the temperature and pressure relief discharge and drain pan drain terminating at a floor drain/floor sink, while the water isometric shows both terminating at the mop sink. Revise the plans for consistency. Reference: Section 107.2.1, IBC 2024.
06/22/2026 Fire New Construction Standard REVIEW COMPLETED
06/16/2026 PDSD Application Completeness Express REVIEW COMPLETED