Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0626-00848
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/21/2026 | Commercial Plumbing Standard | APPROVED | |||
| 08/27/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/19/2026 | Commercial Building Standard | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov 1. Please submit all documents with next submittal. Construction drawings, Rational Analysis, and the Structural Calculations. IBC 107.2.1 Please contact me if you have any questions about the above comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 08/21/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0626-00848 (181 W BROADWAY BL TUCSON, AZ 85701) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Reference sheet EP410, Show the door out of the back electrical room swinging in the direction of egress. NEC 110.26(C)(3). With listed panic hardware for all egress doors from the electrical room. Deferred submittal: Selective coordination report/plans are required prior to the equipment being installed, at risk to the applicant. This can be a deferred submittal with a condition added to the permit. a. Provide electrical sheets/Report showing compliance with selective coordination requirements of NEC sections, Emergency Systems: Article 700.32, Legally Required Standby Systems: Article 701.32, Elevators: Article 620.62. See also NEC 240.11. COT will allow receiving this information after issuance at applicant risk, but Selective Coordination Report is required prior to installation of the equipment. |
||
| 08/19/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Exhaust fans EF-1 through EF-12 are not supplied with emergency power. Show how continuous upward airflow is to be ensured in the exhaust duct shaft. Reference: exception 2, Section 607.5.5, IMC 2024, and Section 909.11, IBC 2024. [Initial comment: Verify that exhaust fans EF-1 through EF-12 are supplied with emergency power. Reference: exception 2, Section 607.5.5, IMC 2024 and Section 909.11, IBC 2024.] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 08/19/2026 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-0626-00848 (181 W BROADWAY BL TUCSON, AZ 85701) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Lumen calculations are incorrect and missing multiple lighting fixtures. Lumen Calculations show 2(two) W2 and 2 W3 fixtures, but Plans show 3 of each fixtures. Update lumen calculations to include 3 of each. Lumen Calculations do not show light pole, P1, in the calculations. Show this fixture in the lumen calculations. 2. Reference sheet el501, lighting fixture W2. show this light fixture as full cutoff and listed for wet locations, similar to the other outdoor lighting fixtures. Show all outdoor lighting fixtures with a maximum of 3500K, OLC 402.1. |
||
| 08/27/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 08/18/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |