Permit Number: TC-COM-0626-00848
Parcel: 11720019C

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0626-00848
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2026 Commercial Building Standard APPROVED
09/08/2026 Commercial Electrical Standard APPROVED Deferred submittal: Selective coordination report/plans are required prior to the equipment being installed, at risk to the applicant. This can be a deferred submittal with a condition added to the permit.
a.Provide electrical sheets/Report showing compliance with selective coordination requirements of NEC sections, Emergency Systems: Article 700.32, Legally Required Standby Systems: Article 701.32, Elevators: Article 620.62. See also NEC 240.11. COT will allow receiving this information after issuance at applicant risk, but Selective Coordination Report is required prior to installation of the equipment.
09/08/2026 Commercial Mechanical Standard APPROVED
09/08/2026 Outdoor Lighting Standard APPROVED
09/09/2026 Restamp Commercial Plumbing APPROVED
09/09/2026 Restamp Site Engineering APPROVED
09/09/2026 Restamp Site Zoning APPROVED
09/09/2026 Restamp Water - PDSD APPROVED
09/14/2026 Bldg Permits - Post Review Express REVIEW COMPLETED
08/31/2026 PDSD Application Completeness Express REVIEW COMPLETED
09/10/2026 Restamp Fire New Construction REVIEW COMPLETED