Permit Number: TC-COM-0626-00847
Parcel: 13419042D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0626-00847
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2026 Commercial Electrical Standard APPROVED
07/06/2026 Commercial Mechanical Standard APPROVED
07/06/2026 Commercial Plumbing Standard APPROVED
07/08/2026 Site Zoning Standard APPROVED Any new signage will require a separate sign permit.
07/06/2026 Water - PDSD Standard APPROVED
07/08/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/18/2026 Site Engineering Standard NOT REQUIRED
07/08/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/07/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
Building Review Comment
1. Sheet A400 Detail 3: Please revise the construction documents to include complete plans and details for the proposed awning, including flashing, roofing, decking, structural connections, and all other information necessary to demonstrate compliance with the 2024 IBC. Additionally, provide structural calculations prepared by the registered design professional demonstrating that the awning is designed to support all applicable loads in accordance with the 2024 IBC. Sufficient information is required to verify code compliance per Section 107.2.7.
Building Review Comment
2. Sheets A503 & A504: Please remove California Building Code references and replace with IBC. IBC 107.2.1 Treat as a typical note.

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
06/22/2026 Fire New Construction Standard REVIEW COMPLETED
06/17/2026 PDSD Application Completeness Express REVIEW COMPLETED