Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0626-00799
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2026 Commercial Electrical Standard APPROVED
06/25/2026 Site Zoning Standard APPROVED
06/26/2026 Water - PDSD Standard APPROVED
06/05/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/25/2026 Site Engineering Standard NOT REQUIRED
06/26/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/17/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Provide the signed and sealed structural calculations, prepared by an Arizona licensed registrant, used in the design of this project. IBC 107.2.7 For example, HVAC support.
2. Sheet G0.0: Please update the list of current codes to replace the referenced 2009 ICC A117.1 standard with the currently adopted 2017 ICC A117.1 edition. IBC 107.2.1
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
06/26/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00799
ADDRESS/PARCEL: 2730 E DREXEL RD Unit:BLDG 2 UNIT 2110 TUCSON, AZ 85706

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:
1. RTU-2110-3 is shown as existing on the mechanical/plumbing sheets but the HVAC unit is shown as new on Sheet S1.0. Is the HVAC unit existing, new, or a replacement. Please clarify. Reference: Section 107.2.1, IBC 2024.
2. The installation of new and replacement commercial HVAC units constitutes new work so the submittal will require a heating/cooling load calculation for the building to justify the capacity of the unit being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The unit itself will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers.
3. A portion of the space has been converted from a warehouse to a showroom. Provide an outdoor air ventilation schedule that shows how the mechanical system meets the minimum outdoor air ventilation requirements for the proposed showroom. Reference: Table 403.3.1.1, IMC 2024.
06/26/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00799
ADDRESS/PARCEL: 2730 E DREXEL RD Unit:BLDG 2 UNIT 2110 TUCSON, AZ 85706

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. New or replacement faucets serving lavatories shall be provided with automatic faucets. Reference: Section 412.13, IPC 2024, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
06/22/2026 Fire New Construction Standard REVIEW COMPLETED
06/04/2026 PDSD Application Completeness Express REVIEW COMPLETED