Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0625-01274
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2025 | Commercial Building Standard | APPROVED | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Approved Reason: Date Completed : 7/18/2025 11:37:33 PM Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 7/11/2025 1:31:03 PM |
||
| 07/14/2025 | Outdoor Lighting Standard | APPROVED | |||
| 07/28/2025 | Water - PDSD Standard | APPROVED | |||
| 07/28/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/21/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Denied Reason: Date Completed : 7/12/2025 4:55:50 PM 1. Comment: Submitted a duplicate upload of electrical design ie there are two sets of electrical designs uploaded. 2. Need to correct the issue of font type for sheet numbers that show up as boxes, making it impossible to determine sheet numbers. This also affects other critical areas ie calculations shown on sheet e5.1. 3. e5.1 ELECTRICAL ONE-LINE DIAGRAM AND DETAILS: Font issues for Fault current calculations. It is difficult to confirm calculations are correct with missing Boxed out information. |
||
| 07/21/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 7/16/2025 11:23:30 AM 1. General - Provide COMcheck Mechanical Compliance Certificate. Any other APPROVED certifying agency is acceptable. - 2018 IECC Section C403.3.2 HVAC equipment performance requirements. ◦ Shell Review only. (If applicable) Kitchen area will require further Mechanical review and Permitting when Grease Hood and MAU is installed. |
||
| 07/21/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 7/20/2025 8:43:42 PM First Plumbing Review-Shell; 1). General Plbg Plans: Missing Primary & secondary storm piping illustrations & calculations for the roof drains shown on Arch roof plan. Add Primary & secondary storm piping illustrations & calculations. -2018 IPC 1106.1, 1106.2, 1106.5, 1108 |
||
| 07/25/2025 | Site Engineering Standard | REQUIRES RESUBMIT | TC-COM-0625-01274 1222 S FREEWAY Site engineering comments are as follows: 1. Please address the differences in the roofed areas from DP20-0269. If these changes are proposed, a revision to the DP will be required. In such case, approval of the building permit will be contingent upon the DP revision’s approval by all reviewers. Ryan Insalaco – ryan.insalaco@tucsonaz.gov |
||
| 07/25/2025 | Site Zoning Standard | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0625-01274 1222 S FREEWAY - C-2 Travelers Accommodation, Lodging (1st Review) TRANSMITTAL DATE: July 25, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-2 zone (UDC 4.7.21). Travelers Accommodation, Lodging is an approved use in the zone (UDC Table 4.8-4). 1. The roofed area shown over the entrance area is not addressed on DP20-0292 and will need to be shown on the DP. Until shown on the DP Zoning cannot approve the building plans. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 07/23/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 07/03/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |