Permit Number: TC-COM-0625-01274
Parcel: 11808009C

Address:
1222 S FREEWAY

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0625-01274
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2025 Commercial Electrical Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 9/30/2025 8:33:29 AM
10/03/2025 Commercial Mechanical Standard APPROVED Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
10/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/03/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 10/3/2025 11:35:12 AM
Second Plumbing Review-Shell;
1). RESOLVED-General Plbg Plans: Missing Primary & secondary storm piping illustrations & calculations for the roof drains
shown on Arch roof plan. Add Primary & secondary storm piping illustrations & calculations. -2018 IPC 1106.1, 1106.2,
1106.5, 1108
2). New Comment Plan Pages P1.2 & A3.2: Now that primary & secondary drain info has been provided, due to the
discharge location of the kitchen Roof the plans are missing the gutter & downspout sizes with the Total GPM Load for that
discharge area. Please add the gutter & downspout sizes with the Total GPM Load for that discharge area. -IPC 1106.3,
1106.6
10/22/2025 Site Engineering Standard REQUIRES RESUBMIT TC-COM-0625-01274
1222 S FREEWAY

Site Engineering Comments are as follows:

1. Please address the Safebuilt comment regarding the dimensions of the downspouts. Please ensure roof drain discharge is maintained under sidewalk.

Ryan Insalaco
Engineering Associate
ryan.insalaco@tucsonaz.gov
10/28/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0625-01274 – DP20-0269
1222 S FREEWAY - C-2
Travelers Accommodation, Lodging (2nd Review)

TRANSMITTAL DATE: ‎October 28, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Travelers Accommodation, Lodging is an approved use in the zone (UDC Table 4.8-4).

1. Previous Comment is still Applicable: The roofed area shown over the entrance area is not addressed on DP20-0269 and will need to be shown on the DP. Until shown on the DP Zoning cannot approve the building plans.

2. Comment: Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov.
09/29/2025 PDSD Application Completeness Express REVIEW COMPLETED