Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0625-01256
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/07/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/07/2025 | Commercial Mechanical | REQUIRES RESUBMIT | ADDRESS/PARCEL: 707 E LEE ST TUCSON, AZ 85719 (UNITS B,E,F,J,K) The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. COMMENTS: 1. The drawing needs to include local exhaust systems and mechanical ventilation systems for outdoor air that meet the requirements of IMC 403.3.2 since you are replacing an Evaporative Cooler with a Packaged Gas/ Electric Unit. Please revise to demonstrate compliance with the ventilation and exhaust rates required. |
||
| 07/30/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |