Permit Number: TC-COM-0625-01226
Parcel: 134102350

Address:
400 S SARNOFF DR

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0625-01226
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2025 Commercial Plumbing APPROVED
07/23/2025 Site Engineering APPROVED
07/25/2025 Site Zoning APPROVED
07/28/2025 Water - PDSD APPROVED
07/28/2025 Commercial Mechanical NOT REQUIRED
07/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/23/2025 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0625-01226
ADDRESS/PARCEL: (400 S SARNOFF DR TUCSON, AZ 85710)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.

COMMENTS:
1. In your Cover Sheet/Front Page, please list the special inspections required for this project IBC 107.2.1 For example, Post installed anchors.
2. Please provide a special inspection certificate with Part A, and Part B completed with next submittal. This form is available in https://www.tucsonaz.gov/files/sharedassets/public/city-services/planning-development-services/documents/special_inspection_certificate.pdf
Ensure that Part B is sealed/signed/dated by the special inspector in charge. Ensure to use Special Inspectors who are active in the approved list of special inspectors. They are available in the following links:
special-inspectors-by-name.pdf (orovalleyaz.gov)
https://content.civicplus.com/api/assets/e426f390-7bd6-4c47-9bc1-357282083afd
https://www.phoenix.gov/pddsite/Documents/TRT/dsd_trt_pdf_00870.pdf
3. The Cover Sheet indicates pre-engineered Steel RAMADA shall be permitted through the City of Tucson DSD via a deferred submittal by the contractor.
a. The RAMADA drawing in the submitted documents are marked Not For Construction and Reference Only.
b. The structural calculations and detail drawings are missing for this RAMADA. Please do make sure to submit it along with the rest of the RAMADA drawings.
c. Just to ensure that we are on the same page, Deferred Submittal to the City of Tucson means a submission will be made to the City of Tucson DSD after the permit has been approved and building permit issued, it will be reviewed/approved for an additional fee with this permit (TC-COM-0625-01226).
d. OR, is the contractor going to submit for a totally separate building permit from this building permit. Please confirm.
4. The Cover Sheet indicates pre-engineered steel SHADE CANOPY shall be permitted through the City of Tucson DSD via a deferred submittal by the contractor.
a. There is sufficient drawings and structural calculation submitted with this package for the city to review. The city suggests reviewing the submitted documents as part of this current review/approval.
b. OR, do you still want the contractor to submit for a totally separate building permit from this building permit. Please confirm.
5. DEFERRED SUBMITTAL: Pre-Fabricated Restroom (***Submit a copy of the State approved Construction Drawings and a copy of the State issued Installation Plan Approval.)
6. Please resubmit.

If you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976
07/14/2025 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0625-01226 (400 S SARNOFF DR TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).


Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. Per the elevations on Sheet A-102 there are 4 exterior LED light fixtures on the pre-fab restroom building. These lights are required to meet the requirements of the Outdoor Lighting Code, OLC 102.4.
2. Fixtures installed under canopies and overhangs. Outdoor lighting fixtures shall not be counted in determining the total light output when they are full cutoff light fixtures installed under canopies, building overhangs, or roof eaves, OLC 401.2.1(3).
3. Show the new lighting fixtures on the pre-fab restroom as full cutoff and under an overhang for exemption from additional outdoor lumen calculations. OR provide the informant below in comments 4-11:
4. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan
5. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
6. Show compliance with total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2.
7. Show compliance with shielding requirements and light trespass per 401.3.
8. Submit catalogue or specification sheets of all proposed new outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded.

9. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

10. Specify any exceptions used.

11. Provide Curfew lighting controls If applicable Per section 403.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/20/2025 Fire New Construction REVIEW COMPLETED
07/11/2025 PDSD Application Completeness Express REVIEW COMPLETED