Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL REVISION v.1
Permit Number - TC-COM-0625-01202
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/06/2025 | Commercial Building Standard | APPROVED | |||
| 11/06/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/05/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0625-01202 ADDRESS/PARCEL: (3210 E VALENCIA RD TUCSON, AZ 85706) COMMENTS 1. The gas piping going to the tankless water heaters appears to be undersized per 2018 IFGC Table 402.4(2). This section now has a demand of 398 MBH, and based on the developed length from the meter, the pipe size should be at least 1 ΒΌ inches. Please resolve. |
||
| 10/16/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |