Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0625-01086
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/26/2025 | Commercial Electrical | APPROVED | |||
| 07/10/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/10/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Supply air delivered to the restroom when the exhaust fan is turned off will result in 100% of the air being circulated to the building. Note g of Table 403.3.1.1 applies when the exhaust is passed through a heat recovery unit; those units have up to 10% leakage of the exhaust to the supply airstream. The exhaust fan should be operating continuously during the hours of operation. This is typically achieved using a time clock. [Initial comment: Provide information on the sequence of operation for the restroom exhaust fans to show that all the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2018.] | ||
| 07/10/2025 | Commercial Plumbing | REQUIRES RESUBMIT | The term “private” for plumbing fixtures applies to fixtures that are located in a residence or apartment, non-public toilet rooms in hotels or motels, and are intended for the use of a family or an individual. The new restroom is required to comply with the requirements of Section C404.5, IECC 2018. Reference: Section 202, IPC 2018. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018 (e.g., 24” for a ½” supply).] | ||
| 06/25/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |