Permit Number: TC-COM-0625-01086
Parcel: 125100500

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0625-01086
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2025 Commercial Electrical APPROVED
07/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/10/2025 Commercial Mechanical REQUIRES RESUBMIT Supply air delivered to the restroom when the exhaust fan is turned off will result in 100% of the air being circulated to the building. Note g of Table 403.3.1.1 applies when the exhaust is passed through a heat recovery unit; those units have up to 10% leakage of the exhaust to the supply airstream. The exhaust fan should be operating continuously during the hours of operation. This is typically achieved using a time clock. [Initial comment: Provide information on the sequence of operation for the restroom exhaust fans to show that all the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2018.]
07/10/2025 Commercial Plumbing REQUIRES RESUBMIT The term “private” for plumbing fixtures applies to fixtures that are located in a residence or apartment, non-public toilet rooms in hotels or motels, and are intended for the use of a family or an individual. The new restroom is required to comply with the requirements of Section C404.5, IECC 2018. Reference: Section 202, IPC 2018. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018 (e.g., 24” for a ½” supply).]
06/25/2025 PDSD Application Completeness Express REVIEW COMPLETED