Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0625-01086
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/12/2025 | Commercial Building | APPROVED | |||
| 06/19/2025 | Site Zoning | APPROVED | |||
| 06/17/2025 | Water - PDSD | APPROVED | |||
| 06/19/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/04/2025 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0625-01086 (3400 E SPEEDWAY BL Unit:UNIT 116 TUCSON, AZ 85716) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide the bus-bar rating of the existing panels, A & B, NEC 408.30 & 408.36. 2. REF Sheet E100: There are multiple receptacle outlets labled ‘TV’ on the Power Plan. Provide the circuit designation associated with these receptacle outlets. Specify if these are subject to wet or damp location requirements, NEC 310.10(B) & (C), NEC 314.15. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 06/17/2025 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Provide ventilation in the Laundry/Storage room (e.g. Retail Storage, Table 403.3.1.1, IMC 2018). Reference: Sections 401.2, 401.3, and 403.3.1.1, IMC 2018. 2. Provide information on the sequence of operation for the restroom exhaust fans to show that all the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2018. 3. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, 504.4 and, 504.6, IMC 2018. |
||
| 06/17/2025 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Provide a metering faucet for the new lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10 seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Provide tempered water for the restroom lavatory using approved devices conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018. 3. Provide a detail of water heater WH-2 installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504 , 606.1, 607.2, and 607.3, IPC 2018. 4. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. clothes washer. The pressure-absorbing devices shall conform to ASSE 1010; an air chamber is not acceptable. Reference: Section 604.9, IPC 2018. 5. Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018 (e.g., 24” for a ½” supply) |
||
| 06/04/2025 | Fire New Construction | REVIEW COMPLETED | Fire Sprinklers upgrades requires a separate submittal and permit | ||
| 06/03/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |