Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0624-01195
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2024 Water - PDSD APPROVED
07/31/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/10/2024 External Reviewers - Stantec REQUIRES RESUBMIT July 9, 2024
1st Review

La Plaza Investors, LLC
Attn: Bruce A. Romano
3900 E. Via Palomita
Tucson, Arizona 85718

Re: SEIS KITCHEN
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0624-01195
Stantec Project Number: 185215066
Stantec File Number: TUC-24-086

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 V-B 7,891 278 Yes No
Separate Permits: Automatic fire sprinklers and kitchen hood suppression system.
Deferred Submittals: Type 1 kitchen hood and Type 2 kitchen hood.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. The plans indicate that a Type 1 kitchen hood and a type 2 kitchen hood will be provided. Please either provide the shop drawings now or list on this sheet as a deferred submittal and include the following notes:

PER IBC Section 107.3.4
<Name of Registrant>, the registered design professional in charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building.

PER IBC Section 107.3.4.1
Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge, who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building.

Sheet A3

1. The occupant load calculation indicates that occupancy for the dining areas and bar has been calculated by counting the number of seats. Occupant load calculations must utilize the corresponding factor in Table 1004.5 unless an appeal is submitted to the building official. [Ref. IBC 2018 Sec. 1004]

2. Please include the outdoor seating areas in the occupant load calculations. The outdoor seating is not shown on the architectural sheets but is show on the MEP sheets. [Ref. IBC 2018 Sec. 1004.7]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

General

1. Please provide an energy conservation compliance report for the new mechanical system. [Ref. IECC 2018 Sec. C403]

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
07/26/2024 Fire New Construction REQUIRES RESUBMIT Address Stantec comments
Questions: patricia.shelton@tucsonaz.gov
07/31/2024 Site Engineering REQUIRES RESUBMIT This project is within a regulated floodplain and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page:
https://tdc-online.tucsonaz.gov/#/home
NOTE: Documentation of a cost estimate from your contractor will be required if this project involves any reconstruction, repair, rehabilitation, structurally connected addition, or other improvement of an existing structure (including TIs and solar). Construction of separate builds/new structures does not require a cost estimate to be provided. Construction of new buildings require elevation one foot above the base flood elevation, which may require that the foundation of the building be raised as much as two feet above the existing elevation onsite. Storage buildings with no utilities may be wet floodproofed using flood vents. For all new construction buildings, two elevation certificates must be filled out by a registered land surveyor and submitted to the City, one before the foundation is poured and one after construction is completed.
Instructions:
1. Navigate into the current project in the “My Work” tab. Within the permit, navigate to the “Sub-Records” tab and click “Apply” on the Floodplain Use Permit Sub-Record
2. Locations -> Confirm the location is accurate to the project. Click “Next”
3. Type -> Fill in the “Square Feet” and “Valuation” boxes with the project area and a contractor-provided cost estimate (See note above: for new structures, input 0). Click “Next”
4. Contacts -> Confirm contacts and add any additional contacts if applicable. Click “Next”
5. More Info -> This will be filled in by the engineer assigned to your case, Click “Next”
6. Attachments -> Please attach the project plan, supporting documentation for the cost estimate (if applicable), and a drainage/hydrology report (if applicable). Click “Next”
7. Signature -> Read the statement and type your name. Sign your name below (You may Enable Type Signature to have the software sign for you.) Click “Next”
8. Review and Submit -> Review all information to ensure accuracy. Click “Submit”

Mike Ortiz
michael.ortiz@tucsonaz.gov
07/24/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0624-01195 - TD-DEV-0524-00159
6530 E TANQUE VERDE RD Unit: 110 - C-2
Food Service (1st Review)

TRANSMITTAL DATE: ‎July 24, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Food service is a permitted use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P.

1. COMMENT: Zoning has reviewed the building plan for compliance with TD-DEV-0323-00183, and the following comments must be addressed prior to approval of the building plans,

2. Show the proposed outdoor seating area on the plan.

3. Zoning cannot approve the building plans until the DP is approved by all review agencies.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
06/26/2024 PDSD Application Completeness Express REVIEW COMPLETED