Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - TC-COM-0624-01146
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/11/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/11/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Please indicate what is new and what is existing shown in the electrical site layout plan. 1a. Is the new electrical service(s) increasing in amp ratings? What was there before? 1b. If the sub-panels are new. Show where they are located in the building and provide panel schedules. 2. Provide a complete electrical line diagram that shows; a. All conduit, conductor, conduit sizes and types. Feeders if applicable. b. Voltage, amp , phase, AIC ratings for the service equipment, including load calculations. c. Show a complete grounding detail for the service(s) and the Guest House. Provide compliance with NEC art 250.58 if applicable. d. Compliance with NEC art 250.32 for the Guest House grounding. e. Show OCPD’s rating in the service equipment that are feeding the subpanels. Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
06/26/2024 | PDSD Application Completeness | REVIEW COMPLETED |