Permit Number: TC-COM-0624-01124
Parcel: 12106001B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0624-01124
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/06/2024 Site Zoning APPROVED
10/28/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/28/2024 External Reviewers - Stantec REQUIRES RESUBMIT October 28, 2024
2nd Review

Medmar Tanque Verde
Attn: Aari Ruben
8060 E. 22nd Street
Tucson, Arizona 85710

Re: 5851 E. SPEEDWAY SUITE 151
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0624-01124
Stantec Project Number: 185215066
Stantec File Number: TUC-24-063

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M III-B 25,600 N/A Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Wood roof strengthening.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. Previous Comment: Note on the cover of the drawings that special inspection is required for wood roof strengthening. Also, the special inspection certification is missing a signature from the owner or legal agent. Still Required: The required special inspections were not included on the cover page of the drawings as requested.

Sheet A3

1. New Comment: The revised plan-set indicates the addition of an exterior exit door for Suite 105. This exterior door is being placed in an exterior load bearing wall. This modification is not reflected on the structural plans and the structural calculations have not been updated. Please have the engineer of record provide updated structural calculations and a revised plan with details on this structural modification.

Sheet A4

1. Addressed.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

Sheet M2

1. Addressed.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E4.0

1. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
08/08/2024 PDSD Application Completeness Express REVIEW COMPLETED