Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0624-01080
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/02/2024 | Site Engineering | APPROVED | |||
| 06/07/2024 | Fire New Construction | NOT REQUIRED | |||
| 07/09/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/08/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Ref; 2012 City of Tucson Outdoor Lighting Code (OLC). 1a Provide compliance with the Curfew Requirements for extinguishing the exterior lighting per OLC section 601.3, controls per section 403.5. 1b Provide for a Special Inspection required per OLC section 106.2.2. Be advised, per COT policy, the Special Inspection certificate must be filled out and the first seal applied by the Special Inspection Registrant responsible for the inspection and submitted prior to permit issue. The Special Inspection must be performed by a qualified Special Inspector per the Pima County Special Inspectors list. 2 The electrical plans show a panel schedule and utilizing panel ‘LA’ for some exterior lighting and other exterior lighting utilizing electrical panel ‘HA’. Provide complete electrical plans including complete electrical line diagrams, grounding details, panel schedules for all breaker panels, location and rating of electrical service equipment, or provide detailed information on the plans as to what scope of work is proposed for this project and what is proposed by different permit or by separate permit by others. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code (OLC). |
||
| 07/09/2024 | Commercial Structural | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. 1. Please provide a copy of the Soils report used in the design of the foundations with the next submittal. IBC 107.2.1 2. Please provide design and calculations prepared by Arizona licensed design professional for the light poles and foundation system shown on Sheet 7 of 10. IBC 107.2.7 Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 06/27/2024 | Site Zoning | REQUIRES RESUBMIT | Until DP TD-DEV-0324-00109 is approved by all review agencies Zoning cannot approve this plan. | ||
| 06/06/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |