Permit Number: TC-COM-0623-01477
Parcel: 11504492A

Address:
901 E 1ST ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0623-01477
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2024 Site Engineering APPROVED
02/15/2024 Site Zoning APPROVED
02/22/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/21/2024 Commercial Structural REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0623-01477
ADDRESS/PARCEL: 901 E 1ST ST TUCSON, AZ 85719
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. As I recall, the Church wanted gutter installed at the back end of the canopy. This new drawing does not show gutter, please correct this.
2. The depth of the canopy from the original drawings is 17 ft including the gutter. This new drawing does not reflect this. Please correct.
3. The original drawings shows 124 ft overall length, this new drawing shows 180 ft. Please correct this.
4. The new drawings does not match the originally approved structural calculations and design by PK Associates LLC dated 5/17/23 Structural Engineer Robert Halliday. For example, the original showed the posts in the middle, this new drawing shows the posts to one side. Please coordinate this -or- submit a revised Structural Design & Calculations. Please correct this.
5. Please resubmit
02/15/2024 Fire New Construction REVIEW COMPLETED
02/13/2024 PDSD Application Completeness REVIEW COMPLETED