Permit Number: TC-COM-0526-00785
Parcel: 14117008A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0526-00785
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2026 Commercial Building Standard APPROVED COMMENTS:
1. THE COMMERCIAL BUILDING REVIEW HAS BEEN APPROVED w/ the following request.
2. DRAWING SET COORDINATION FOR CLARITY:
a. The Index of Drawings lists 30 Architectural sheets.
i. However, the actual Architectural sheets submitted within the set of drawings totals 38.
ii. I noticed that there are multiples sheets of the same sheet. For example, there are two of A1.5, A3.6, A5.0, A51, A5.2, A5.3, A5.4 and A5.5
iii. Is it possible that some of these sheets have been revised and the previous drawing sheets were of the old/previous version that did not get removed?
b. Above Ground BR 5500 details SHEET has a sheet number of “A” on the title block. However, the Index of Drawings have is as “BR55”. May we suggest this be coordinated for clarity.
c. Plumbing Roofing Plan does not have a sheet number on the title block.
3. MEN’S RESTROOM
a. Yes, we agree with you. The stall do comply with the 60” x 56” clear floor area for the water closet.
b. As for the 67” turning space, I dropped a 67” circle in front of the lavatory and it looks like there is space to accomplish this.
c. Please show this 67” turning space in front of the lavatory please.
4. Other reviewers have requested corrections to be made, please include the above request for clarification purposes.
08/14/2026 Commercial Electrical Standard APPROVED Approved with comments added on plans:
2023 NEC Article 511 Commercial Garages, Repair and Storage
511.3 Area Classification, General.

Where Class I liquids or gaseous fuels are stored, handled, or transferred, electrical wiring and electrical utilization equipment shall be designed in accordance with the requirements for Class I, Division 1 or 2 hazardous (classified) locations as classified in accordance with 500.5 and 500.6, and this article.

All Welders to comply with 2023 NEC Article 630.
08/14/2026 Outdoor Lighting Standard APPROVED
08/24/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/21/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0526-00785
ADDRESS/PARCEL: 7655 S HOUGHTON RD TUCSON, AZ 85747

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Mechanical Sheets M1, M2, and M4: Some of the text is not fully legible. Please ensure all information is clear and legible.
2. Please include the revised heating/cooling calculations in the plan set or as a separate sheet. Please do not provide the calculations only in the response letter.
08/21/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0526-00785
ADDRESS/PARCEL: 7655 S HOUGHTON RD TUCSON, AZ 85747

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. The sheet label is missing for the Plumbing Roof Plan (Sheet P2.1). Please provide the sheet label.
07/31/2026 Site Engineering Standard REQUIRES RESUBMIT Permit Activity Number: TC-COM-0526-00785 (2nd Review)
Project: New paint and auto body repair facility.
Location: 7655 S HOUGHTON RD
Review Date: 7/31/2026
Reviewer: Marco Contreras – Engineering Associate - Site Engineering
Reviewer Contact: Marco.contreras@tucsonaz.gov
Related cases:

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed to ensure final approval from Site Engineering.
To help speed up your resubmittal and facilitate shorter review timelines, please include a response letter along with your updated plans and any supporting calculations. In your response letter, address each comment individually and explain what changes were made and where they can be found in the plans. Please do not mark or highlight changes in the drawings at this stage — revision markups are only used after a permit has been issued. Submit your response letter and updated plan set as two separate files.
Site Engineering Review Comments:
1. Previous comment not address nor acknowledged - The proposed new paint and auto body repair facility constitutes a new site with associated required site development work, and therefore requires submission of a Development Package (DP) in accordance with UDC §7.4.3.E. Per UDC §3.3.3.G.2.c, A full DP submittal meeting the requirements for Commercial/Industrial sites is required, and must include at minimum: a site plan drawn to scale showing all proposed and existing improvements, property line and setback dimensions, vehicular use areas, and adjacent streets; a grading and drainage plan with supporting drainage report addressing on-site retention/detention and off-site discharge per City of Tucson Drainage Design Standards; a geotechnical (soils) report addressing soil suitability, bearing capacity, and any special foundation recommendations; a landscape and irrigation plan meeting Landscaping requirements; and utility plans showing water, sewer, and any required easements or extensions.
a. Please coordinate through email to confirm any additional studies required based on site conditions & reviewer comments. Note that the Development Package is a separate permit submittal, and must be processed independently of, the building plans.
2. Site Engineering is unable to fully review and approve permit TC-COM-0526-00785 until the associated Development Package is reviewed and approved by all reviewers.
08/18/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Krista Hansen
Planning & Development Services Department – Zoning Review Section

PROJECT: TC-COM-0526-00785
7655 S Houghton Rd
New Paint and Autobody Repair Shop (2nd Review)

TRANSMITTAL DATE: 8/18/2026


This site is zoned I-2 (UDC Section 4.7.30).


Resubmit revised drawings with a response letter stating how all Zoning Review Section comments were addressed.

1. Previous Comment 1 was not addressed: “As you are proposing a new building and associated parking lot, a Development Package (DP) will be required. Per UDC Article 3.3.3.G.2.c, a site plan (DP) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A DP meeting the minimum requirements is required to be submitted and approved. The DP is a separate submittal from the building plans. Site zoning is unable to approve this building permit until the DP has been approved by all reviewers.”

Follow Up: This comment still stands.

2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

For questions regarding Zoning comments, please contact me at: Krista.Hansen@tucsonaz.gov
08/21/2026 Water - PDSD Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0526-00785
ADDRESS/PARCEL: 7655 S HOUGHTON RD TUCSON, AZ 85747

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Previous comment not addressed. [Initial comment - Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water (i.e. not inside of a building, see detail 04/P3.1). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf] See Plumbing Floor Plan, Sheet P2.0, as well.
08/20/2026 Fire New Construction Standard REVIEW COMPLETED
07/29/2026 PDSD Application Completeness Express REVIEW COMPLETED