Permit Number: TC-COM-0526-00785
Parcel: 14117008A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0526-00785
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/21/2026 Restamp Commercial Energy PENDING ASSIGNMENT
10/20/2026 Commercial Mechanical Standard REQUIRES RESUBMIT Comment not resolved. RTU-2 is located approximately one half-fan diameter away from the fan blades. The fan manufacturer requires HVAC diffusers located above or below the fan blades to have one fan diameter of clearance from the fan blades. (https://bigassfans.widen.net/s/vvdl92lnm2/industrial-overhead-install-checklist) Note: the manufacturer must be consulted if the fan blades are located at the same level as the HVAC diffuser.
[Initial comment: Show that the HVLS fan is being installed in accordance with the conditions of its listing and the manufacturer’s installation requirements with regard to its proximity to the supply air drop box for RTU-2. Reference: Section 304.1, IMC 2024.]

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
10/20/2026 Commercial Plumbing Standard REQUIRES RESUBMIT Revise the location of the reduced pressure backflow preventer to a location accessible to Tucson Water.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
10/13/2026 Site Engineering Standard REQUIRES RESUBMIT Permit Activity Number: TC-COM-0526-00785 (3rd Review)
Project: New paint and auto body repair facility.
Location: 7655 S HOUGHTON RD
Review Date: 10/13/2026
Reviewer: John Mounsey – Engineering Associate
Reviewer Contact Information: john.mounsey@tucsonaz.gov

Site Engineering Comments:
1. Site Engineering has completed its review of the submitted plan set and cross-referenced it against the associated development package. However, Site Engineering is unable to grant final approval for Commercial Permit: TC-COM-0526-00785 until the associated revision to Development Package TD-DEV-0324-00092 has received full approval and has been issued. Please resubmit for final approval once the development package has been approved and issued by all applicable reviewers. For final approval - Ensure that all building plans match what is shown in the development package plan set.
10/21/2026 Site Zoning Standard REQUIRES RESUBMIT FROM: Olga Salazar
PDSD Zoning Review Section

PROJECT: TC-COM-0526-00785
New Paint and Autobody Repair Shop (3rd Review)
7655 S. Houghton Rd.

TRANSMITTAL DATE: October 21, 2026

This site is located in the I-2 zone (UDC 4.7.30). Trade Service and Repair – Major is an allowed use in this zone (UDC Table 4.8-5) subject to Use Specific Standards 4.9.4.X.1 and 4.9.13.Q.

1. COMMENTS: Site Zoning has reviewed the plans for compliance with the associated Development Package (DP) TD-DEV-0324-00092. While it appears the building plans match the DP, Site Zoning cannot approve this permit until the current DP revision is approved by all review agencies.

2. COMMENT: For final approval, please ensure that the building plans are consistent with the building footprint, proposed height, and square footage shown on the associated DP.

3. COMMENT: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.


If you have any questions about this transmittal, contact Olga Salazar at Olga.Salazar@tucsonaz.gov.
10/20/2026 Water - PDSD Standard REQUIRES RESUBMIT Previous comment not addressed. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water (i.e. not inside of a building, see detail 04/P3.1 and P2.0). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
09/30/2026 PDSD Application Completeness Express REVIEW COMPLETED