Permit Number: TC-COM-0526-00767
Parcel: 13213034D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0526-00767
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2026 Commercial Electrical Standard APPROVED Stantec Reviewing
06/12/2026 Commercial Mechanical Standard APPROVED Stantec Reviewing
06/17/2026 Site Zoning Standard APPROVED
06/15/2026 Water - PDSD Standard APPROVED
06/12/2026 Commercial Plumbing Standard NOT REQUIRED Stantec Reviewing
05/29/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/02/2026 Site Engineering Standard NOT REQUIRED
06/18/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/12/2026 Commercial Building Standard REQUIRES RESUBMIT June 11, 2026
1st Review

Swaim and Associates
Attn: Kevin Barber
7350 E. Speedway Blvd., 210
Tucson, Arizona 85710

Re: THE REFINERY – FIRST FLOOR
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0526-00767
Stantec Project Number: 185215066
Stantec File Number: TUC-26-037

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. When sending responses to the City through the portal, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B II-B 120,313 187 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm
Deferred Submittals: None
Special Inspections: None

ARCHITECTURAL COMMENTS

Sheet g1.0

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and the fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as separate permits (not as deferred submittals to this permit). The plans currently indicate that these systems are to be submitted as a deferred submittal to this permit.

Sheet a0.0

1. The right side of the floor plan indicates that there is an enlargement of the floor plan on Sheet a1.2, however there is no Sheet a1.2 in the set. Looking at the sheet index on Sheet g1.0 there is no Sheet a1.2 planned in the set. Looking at the floor plan on Sheet a1.1, the key plan does not match the floor plan. For example, the restrooms in the upper left corner of the partial plan are not highlighted on the key plan. Please coordinate. {The key plans in the mechanical and electrical sheets are correct and show the east and west plan halves. Looks like architecturally all of the work was presented on an expanded west floor plan.}

MECHANICAL COMMENTS

There are no mechanical comments.

ELECTRICAL COMMENTS

There are no electrical comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
06/18/2026 Fire New Construction Standard REVIEW COMPLETED
05/28/2026 PDSD Application Completeness Express REVIEW COMPLETED