Permit Details

Status:
Issued
Type:
Commercial Building
Apply Date:
05/26/2026
Applicant:
Eric Fike
Description:
Remodel to existing tenant space

Permit Reviews

Permit Number - TC-COM-0526-00767
Permit Status: Issued
Permit Description: Remodel to existing tenant space
Start Date Submittal Complete Date Status  
07/06/2026 ADMINISTRATIVE v.1 07/06/2026 REQUIRES RESUBMIT Review Details
05/28/2026 COMMERCIAL REVIEW - FULL v.1 06/18/2026 REQUIRES RESUBMIT Review Details
06/23/2026 COMMERCIAL REVIEW - FULL v.2 07/06/2026 APPROVED Review Details
09/11/2026 BUILDING DEFERRED SUBMITTAL REVIEW v.1 09/15/2026 APPROVED Review Details

Conditions

Permit Number - TC-COM-0526-00767
Permit Status: Issued
Permit Description: Remodel to existing tenant space
Date Description Comments
07/01/2026 AIR BALANCING REPORT IS REQUIRED.
05/28/2026 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
05/28/2026 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-0526-00767
Permite Description: Remodel to existing tenant space
Total Outstanding Inspections - 7
Last Inspection Date Description Inspector Results Comments
07/31/2026 COT - HCEL - Electrical Intermediate N/A Partial Pass 7-31-26: in wall electrical intermediate/framing at room's 154, 164A, 164B, 154, 145B, 145C, 145D, 180A, 180B, 176, 177 are okay to insulate and drywall. Schedule a drywall screw inspection prior to tape & texture.
07/31/2026 COT - HCBU - Framing N/A Partial Pass 7-31-26: in wall electrical intermediate/framing at room's 154, 164A, 164B, 154, 145B, 145C, 145D, 180A, 180B, 176, 177 are okay to insulate and drywall. Schedule a drywall screw inspection prior to tape & texture.
08/05/2026 BULD - Electrical Clearance N/A Not Applicable
08/24/2026 COT - HCEL - Electrical Above Ceiling N/A Partial Pass 8/24/2026 Partial pass. Office spaces 180A,180B,164B,164A,154,145D,145B,145C.
08/24/2026 COT - HCME - Mechanical Above Ceiling N/A Partial Pass 8/24/2026 Partial pass. Office spaces 180A,180B,164B,164A,154,145D,145B,145C.
08/24/2026 COT - HCBU - Building Above Ceiling N/A Partial Pass 8/24/2026 Partial pass. Office spaces 180A,180B,164B,164A,154,145D,145B,145C.
09/03/2026 ENGR Engineering Final N/A Partial Pass Air Balancing condition is not satisfied. This must be satisfied prior to final.
Site is clear and complete.
It is recommended that address numbers are placed on Building per Tucson City Code Sec 16-12. Address Display for commercial buildings.