Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0526-00755
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2026 Commercial Mechanical Standard NOT REQUIRED
06/08/2026 Commercial Plumbing Standard NOT REQUIRED
05/29/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/02/2026 Site Engineering Standard NOT REQUIRED
06/11/2026 Site Zoning Standard NOT REQUIRED
06/08/2026 Water - PDSD Standard NOT REQUIRED
06/16/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/08/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please indicate how 4000 Psi was determined for the allowable Compressive Strength of the existing Concrete slab. IBC 107.2.3
2. Please provide a project specific statement of special inspections for this project, stating requirements for the special inspections and required tests. IBC 107.2.1, IBC 1704, IBC 1705 For example, Post-Installed Anchors (HILTI KWIK BOLT TZ2,OR EQUAL (1) PER BASEPLATE.
Additionally, provide the City of Tucson Special Inspection Certificate(s) with Parts A and B
completed with the next submittal. IBC 107.1 SI form link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
06/04/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0526-00755 (2730 E DREXEL RD Unit:BLDG 2 UNIT 2110 TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide a lighting plan showing where the existing lighting fixtures are located. Indicate if any are required to be moved or relocated due to the new shelving.
2. Show sufficient lighting levels at the ground level once the shelving and storage materials are installed. Show 1 footcandle of illumination at the walking surface between the new shelving, IBC 1008.2.1.
3. Show any other electrical devices, receptacles, etc. that may require to be relocated.
06/16/2026 Fire New Construction Standard REVIEW COMPLETED
05/26/2026 PDSD Application Completeness Express REVIEW COMPLETED