Permit Number: TC-COM-0526-00730
Parcel: 12216115B

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0526-00730
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/19/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding this review, please contact CDRC@tucsonaz.gov.

Your site plan needs to include the full property address. Please resubmit your construction plans with the property address included on each page after other reviews are completed.

Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
05/20/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0526-00730 (2351 N ALVERNON WY Unit:BLDG 1 TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The conductors to the ‘Existing NW Building SES’ appear to be undersized for the given connected loads. The given connected loads is 700A, while 2 sets of #300KCMIL CU conductors is only rated at 560A. Please clarify and provide conductors rated for the calculated loads, NEC 230.23.
2. Please provide updated EOR seals for the changes made on the plans.
05/19/2026 PDSD Application Completeness Express REVIEW COMPLETED