Permit Number: TC-COM-0526-00706
Parcel: 115051500

Address:
2226 N STONE AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0526-00706
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2026 Commercial Building Standard APPROVED
06/05/2026 Site Zoning Standard APPROVED
06/03/2026 Water - PDSD Standard APPROVED
05/20/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
05/22/2026 Site Engineering Standard NOT REQUIRED
06/06/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/27/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0526-00706 (2226 N STONE AV TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Show the location of the two services that are being demo’ed and removed.
2. Clarify the ‘Existing SES’ that feeds the Existing Panel ‘A’. Is this service powering a separate unit?
a. Street view of this service and the conduit to Panel ‘A’, shows that the conduit from the Existing SES to Panel ‘A’ has been damaged and moved illegally. This conduit needs to be fixed and brought back into compliance with the existing electrical code.
3. Lighting Keynote #2, on the lighting plan, does not point to anything. Please correct.
4. Reference sheet E1, 1 line diagram. Missing keynote #3. This note is shown on the line diagram, but missing from the actual notes.
5. Provide GFCI protection for Circuits ‘B-22’ & ‘C-22’, NEC 210.8(B)(7) & (14).
6. Show a GFCI and weather protected receptacle outlet on the same level within 25’ of exterior HVAC equipment, NEC 210.62. New HVAC unit added to roof.
06/04/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Verify the exhaust flowrate for the detailing room, including the area of the southern entry. Reference: Section 403.3.1.1, IMC 2024.
2. If the vehicles in the repair garage will be operated more than during the time required to move the vehicle in and out of the room, provide a design for the source-capture exhaust system for operating motor vehicles. Reference: Section 502.14, IMC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
06/03/2026 Commercial Plumbing Standard REQUIRES RESUBMIT Provide calculations to show that capacity of the proposed sand/oil separator complies with the requirement of Section 1003.4.2.2, IPC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
06/06/2026 Fire New Construction Standard REVIEW COMPLETED
05/14/2026 PDSD Application Completeness Express REVIEW COMPLETED