Permit Number: TC-COM-0525-01025
Parcel: 13014023A

Address:
4220 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0525-01025
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2025 Water - PDSD Standard APPROVED
07/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/27/2025 Commercial Building Standard REQUIRES RESUBMIT Structural(S) Reviewer
Nicholas Baptiste
njnobaptiste@safebuilt.com
Denied
Reason:
Date Completed : 6/25/2025 9:41:43 PM
1. A550 (Partition Types) / Information Required. Sections on this sheet show diagonal bracing at the head of the interior
wall partitions. Provide additional details/information such as the section size and connection detail to top of wall and
to the structure.
2. S002 (Schedule) / Information Required. The Masonry Column Schedule detail depicts an MC 0824, but the details
are not provided in the schedule . Provide a revise schedule including MC 0824.


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/19/2025 4:56:57 PM
06/27/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 6/23/2025 12:11:44 PM
1. E202 Floor Plan - Express Building: Need to provide an interior lighting comcheck to show IECC compliance.
2. E301a RCP - Showroom: Need to provide an interior lighting comcheck for 1st floor and mezzanine to show IECC
compliance.
3. E301a RCP - Showroom: Need to perform a Tucson exterior lighting/lumens calculation to show compliance with
current Tucson exterior lighting requirements for all exterior lighting replacements.
4. E400 Panelboard Schedules: Feeder is undersized for 400 amp Disconnect for MDP (should be 2 sets of feeders).
5. E400 Panelboard Schedules: Need to call out feeder for Panel LSB.
6. E400 Panelboard Schedules: Need to provide short circuit (fault current) calculations for new panels per Tucson city
requirements. Local utilities provide fault tables for reference for their installed transformers to use for service fault
calculations. However, Engineer of Record (EOR) is allowed to use the service transformer spec to determine a more
accurate fault current (Utility provide values are conservative) if EOR so chooses.
7. E401 Panelboard Schedules: Need to provide missing panel schedule MA.
06/27/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical(M) Reviewer
John Graves
jgraves@mtcinspectors.com
Denied
Reason:
Date Completed : 6/19/2025 3:04:43 PM
1) 2018 Intermanional mechanical code as amended by city of Tucson ,AZ code section M312.1. .2018 International Energy
Conservation Code as amended by city of Tucson, AZ C403.3.1. Provide load calculations for additional areas added to
existing spaces.
2) 2018 Intermanional Mechanical Code as amended by city of Tucson ,AZ code section M403.3.1. 2018 International
Energy Conversation Code as aamended by the city of Tucson, AZ. C403.3.1. Provide outside air calculations and quantity.
for all occupied spaces.
3) 2018 International Coservation Code as amendnded by the city of Tucson, AZ. code section C501.7(2) Provide AHRI
certificate of performance for all air conditioning equipment..
4) 2018 International Coservation Code as amendnded by the city of Tucson, AZ. code section C408.2.2 Provide Test and
Balance report for all air conditioned areas.
For questions on mechanical review contact John Graves by phone at 786 918 3715 or e mail jgraves@mtcinspectors.com .
06/27/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 6/26/2025 10:43:06 PM
FIRST PLUMBING REVIEW:
1). Plan page P203: Missing Existing roof leader size adjacent to new high roof (only list roof drain assembly size) Add
Existing roof leader size adjacent to new high roof -2018 IPC 1106.2
2). Plan pages P003, P203, P301a & P301b: Missing gas sizing calculation table used. Add gas sizing calculation table used.
-2018 IFCG 402.3
3). General All Plumbing pages: Missing Shut off valves at Hose Bibs. Add Shut off valves at Hose Bibs.. -2018 IPC 606.2
4). Plan Page P001: Missing sand/oil inceptor sizing calculations. . Add Sand/oil interceptor Sizing calculations.-2018 IPC
1003.4.2.2
5). Plan Page P001: Missing Piping material information. Add Piping material information. -2018 IPC 605.4, 702, 1102, 2018
IFGC 403
6). Plan Page P001 : Missing Coffee Maker Backflow information. Add Coffee Maker Backflow information.-2018 IPC ,
608.17.1
07/08/2025 Fire New Construction Standard REQUIRES RESUBMIT -Correct the adopted IFC year in you applicable codes, sheet G003. TFD/COT has adopted the 2024 IFC with amendments.
-Indicate if building has an existing building fire alarm. You mention it in your deferred submittals but there are no other notes indicated an existing fire alarm. Please include on sheet G003.
john.vincent@tucsonaz.gov
5203495581
06/26/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Permit Review TC-COM-0525-01025 (4220 E 22ND ST TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. The modification/replacement of the exterior lighting fixtures, W1,W2,W3, require compliance with the outdoor lighting code, OLC 102.4.2. See Exception to OLC 102.4.2.
2. Provide the specification sheets for fixtures W1,W2,W3 and show lumens at 2000, color temperature no greater than 3500 Kelvin, and fully shielded.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/14/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-0525-01025
Location: 4220 E 22ND ST
Site Engineering Comments:
1. Final Site Engineering approval of permit TC-COM-0525-01025 cannot occur until the development package TD-DEV-0425-00111, is approved

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
07/09/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0525-01025
4220 E 22nd St. Tucson, AZ 85711
Renovation of existing Chrysler Dodge Ram Fiat dealership (1st Review)

TRANSMITTAL DATE: 7/9/2025

This site is located in the C-2 zone (UDC 4.7.21). Vehicle rental and sales is a permitted use in the zone (UDC Table 4.8-4) subject to Use Specific Standard 4.9.9.G.1 & 2.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Zoning has reviewed the building permit for compliance with development package (DP) TD-DEV-0425-00111, and although it appears that the building plan is in compliance, until the DP is approved by all review agencies zoning cannot approve this plan.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
05/21/2025 PDSD Application Completeness Express REVIEW COMPLETED