Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0525-01025
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/10/2025 | Water - PDSD Standard | APPROVED | |||
| 07/14/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/27/2025 | Commercial Building Standard | REQUIRES RESUBMIT | Structural(S) Reviewer Nicholas Baptiste njnobaptiste@safebuilt.com Denied Reason: Date Completed : 6/25/2025 9:41:43 PM 1. A550 (Partition Types) / Information Required. Sections on this sheet show diagonal bracing at the head of the interior wall partitions. Provide additional details/information such as the section size and connection detail to top of wall and to the structure. 2. S002 (Schedule) / Information Required. The Masonry Column Schedule detail depicts an MC 0824, but the details are not provided in the schedule . Provide a revise schedule including MC 0824. Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 6/19/2025 4:56:57 PM |
||
| 06/27/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Denied Reason: Date Completed : 6/23/2025 12:11:44 PM 1. E202 Floor Plan - Express Building: Need to provide an interior lighting comcheck to show IECC compliance. 2. E301a RCP - Showroom: Need to provide an interior lighting comcheck for 1st floor and mezzanine to show IECC compliance. 3. E301a RCP - Showroom: Need to perform a Tucson exterior lighting/lumens calculation to show compliance with current Tucson exterior lighting requirements for all exterior lighting replacements. 4. E400 Panelboard Schedules: Feeder is undersized for 400 amp Disconnect for MDP (should be 2 sets of feeders). 5. E400 Panelboard Schedules: Need to call out feeder for Panel LSB. 6. E400 Panelboard Schedules: Need to provide short circuit (fault current) calculations for new panels per Tucson city requirements. Local utilities provide fault tables for reference for their installed transformers to use for service fault calculations. However, Engineer of Record (EOR) is allowed to use the service transformer spec to determine a more accurate fault current (Utility provide values are conservative) if EOR so chooses. 7. E401 Panelboard Schedules: Need to provide missing panel schedule MA. |
||
| 06/27/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Mechanical(M) Reviewer John Graves jgraves@mtcinspectors.com Denied Reason: Date Completed : 6/19/2025 3:04:43 PM 1) 2018 Intermanional mechanical code as amended by city of Tucson ,AZ code section M312.1. .2018 International Energy Conservation Code as amended by city of Tucson, AZ C403.3.1. Provide load calculations for additional areas added to existing spaces. 2) 2018 Intermanional Mechanical Code as amended by city of Tucson ,AZ code section M403.3.1. 2018 International Energy Conversation Code as aamended by the city of Tucson, AZ. C403.3.1. Provide outside air calculations and quantity. for all occupied spaces. 3) 2018 International Coservation Code as amendnded by the city of Tucson, AZ. code section C501.7(2) Provide AHRI certificate of performance for all air conditioning equipment.. 4) 2018 International Coservation Code as amendnded by the city of Tucson, AZ. code section C408.2.2 Provide Test and Balance report for all air conditioned areas. For questions on mechanical review contact John Graves by phone at 786 918 3715 or e mail jgraves@mtcinspectors.com . |
||
| 06/27/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 6/26/2025 10:43:06 PM FIRST PLUMBING REVIEW: 1). Plan page P203: Missing Existing roof leader size adjacent to new high roof (only list roof drain assembly size) Add Existing roof leader size adjacent to new high roof -2018 IPC 1106.2 2). Plan pages P003, P203, P301a & P301b: Missing gas sizing calculation table used. Add gas sizing calculation table used. -2018 IFCG 402.3 3). General All Plumbing pages: Missing Shut off valves at Hose Bibs. Add Shut off valves at Hose Bibs.. -2018 IPC 606.2 4). Plan Page P001: Missing sand/oil inceptor sizing calculations. . Add Sand/oil interceptor Sizing calculations.-2018 IPC 1003.4.2.2 5). Plan Page P001: Missing Piping material information. Add Piping material information. -2018 IPC 605.4, 702, 1102, 2018 IFGC 403 6). Plan Page P001 : Missing Coffee Maker Backflow information. Add Coffee Maker Backflow information.-2018 IPC , 608.17.1 |
||
| 07/08/2025 | Fire New Construction Standard | REQUIRES RESUBMIT | -Correct the adopted IFC year in you applicable codes, sheet G003. TFD/COT has adopted the 2024 IFC with amendments. -Indicate if building has an existing building fire alarm. You mention it in your deferred submittals but there are no other notes indicated an existing fire alarm. Please include on sheet G003. john.vincent@tucsonaz.gov 5203495581 |
||
| 06/26/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Permit Review TC-COM-0525-01025 (4220 E 22ND ST TUCSON, AZ 85711) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Review: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf 1. The modification/replacement of the exterior lighting fixtures, W1,W2,W3, require compliance with the outdoor lighting code, OLC 102.4.2. See Exception to OLC 102.4.2. 2. Provide the specification sheets for fixtures W1,W2,W3 and show lumens at 2000, color temperature no greater than 3500 Kelvin, and fully shielded. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 07/14/2025 | Site Engineering Standard | REQUIRES RESUBMIT | Permit: TC-COM-0525-01025 Location: 4220 E 22ND ST Site Engineering Comments: 1. Final Site Engineering approval of permit TC-COM-0525-01025 cannot occur until the development package TD-DEV-0425-00111, is approved If you have any questions or concerns, please contact Marco Contreras Marco.contreras@tucsonaz.gov |
||
| 07/09/2025 | Site Zoning Standard | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Bobby Parsons Zoning Section Review PROJECT: TC-COM-0525-01025 4220 E 22nd St. Tucson, AZ 85711 Renovation of existing Chrysler Dodge Ram Fiat dealership (1st Review) TRANSMITTAL DATE: 7/9/2025 This site is located in the C-2 zone (UDC 4.7.21). Vehicle rental and sales is a permitted use in the zone (UDC Table 4.8-4) subject to Use Specific Standard 4.9.9.G.1 & 2. Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed. 1. Comment: Zoning has reviewed the building permit for compliance with development package (DP) TD-DEV-0425-00111, and although it appears that the building plan is in compliance, until the DP is approved by all review agencies zoning cannot approve this plan. If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov. |
||
| 05/21/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |