Permit Number: TC-COM-0525-01016
Parcel: 116206340

Address:
115 S LINDA AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0525-01016
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2026 Commercial Mechanical Standard APPROVED
06/23/2026 Design Review Standard APPROVED PDF file of Design Professional's review is available in the TDC account and PRO. The design has been refined since the original Design Package approval but still meets the overall building design that was approved.
06/12/2026 Site Engineering Standard APPROVED
06/15/2026 Water - PDSD Standard APPROVED
06/02/2026 Commercial Electrical Standard NOT REQUIRED
06/02/2026 Commercial Plumbing Standard NOT REQUIRED
06/02/2026 Outdoor Lighting Standard NOT REQUIRED
06/23/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/02/2026 Commercial Building Standard REQUIRES RESUBMIT June 2, 2026
1st Review

Lizard Rock Designs
Attn: Carina Eichorst
1640 E. River Road, Suite 206
Tucson Arizona 85718

Re: LINDA AVENUE APARTMENTS
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-0525-01016
Stantec Project Number: 185215066
Stantec File Number: TUC-26-034

Plan review for the project referenced above has been completed. This letter reflects comments to be addressed. PLEASE send all responses to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-2 V-B 38,548 174 Yes Yes
B
S-2
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: Wood trusses.
Special Inspections: Earthwork, epoxy and expansion anchors, and fabricated systems and elements.

ARCHITECTURAL COMMENTS

Sheet G1.5

1. The calculated fire rating performed in Detail 4 is incorrect. Per 2018 IBC Sec. 722.6.2.1, the calculation can only include the fire side membrane and the framing; the non-fire side membrane cannot be included. For a floor you can only include the lower membrane and the framing; you cannot include the upper membrane. The calculation should total 60 minutes and not 75 minutes. That said, per 2018 IBC Sec. 722.6.2.4, the upper membrane of this floor assembly must at a minimum meet the requirements of Table 722.6.2(4). The detail references the structural drawings for the floor deck, and the structural drawings indicate that the floor deck is 3/4" T&G WSP; this meets the requirement of the table.

Sheet A8.0

1. The second layer of gypsum board has been removed from the bottom of the stairs, which is acceptable. However, what is the construction of the ceiling and walls enclosing Riser 128? Per 2018 IBC Sec. 1011.7.3 the walls and floor/ceiling of this enclosed space under the stairs need to be 1-hour fire resistance rated, and the plans are not clear. {The First Floor Exiting Plan on Sheet G1.1 does show 1-hour walls; but ceiling is not clear.}


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
06/12/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0525-01016 - TD-DEV-0325-00070
115 S. Linda Ave Tucson, AZ 85745
New 3 story multi-family residential building (1st Revision Review)

TRANSMITTAL DATE: 6/12/2026

This site is located in the C-1/C-2 zone (UDC 4.7.20 & 4.7.21). Multifamily is an approved use in the zone (UDC Table 4.8-4).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Site zoning has reviewed the plans for compliance with the associated Development Package (DP) TD-DEV-0325-00070. While it appears the building plans match the DP, Site Zoning cannot approve this permit until the revised DP is approved by all review agencies.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
06/17/2026 Fire New Construction Standard REVIEW COMPLETED
05/27/2026 PDSD Application Completeness Express REVIEW COMPLETED