Permit Number: TC-COM-0525-01005
Parcel: 141019160

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0525-01005
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2026 Commercial Building Standard APPROVED Structural (S) Reviewer
Andrew Bevis; abevis@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 2/4/2026

Building (B) Reviewer
Andrew Bevis; abevis@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 2/4/2026
02/05/2026 Commercial Mechanical Standard APPROVED Mechanical (M) Reviewer
Jorge Valido; jvalido@safebuilt.com
Discipline Status:Approved with Comments
Date Completed: 2/5/2026
No Mechanical in this Revision.
02/05/2026 Commercial Plumbing Standard APPROVED Plumbing (P) Reviewer
Andrew Bevis; abevis@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 2/4/2026
02/10/2026 Outdoor Lighting Standard APPROVED
02/24/2026 Water - PDSD Standard APPROVED
02/25/2026 Site Zoning Standard NOT REQUIRED
02/25/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/05/2026 Commercial Electrical Standard REQUIRES RESUBMIT Electrical (E) Reviewer
Ron Ross; rross@safebuilt.com
Discipline Status:Denied
Date Completed: 2/3/2026
ES1.2: Need to provide a Tucson City Outdoor Lighting Code Ordinance exterior lumens per acre calculation to show
continued compliance as the new design has added a couple of extra fixtures.
02/25/2026 Site Engineering Standard REQUIRES RESUBMIT Site Engineering Review

TC-COM-0525-01005
5651 S HOUGHTON RD

Description: New McDonald's building

Site Engineering comments are as follows:

1. This commercial building permit cannot be approved until the revision to the associated development package, TD-DEV-0525-00132, is approved by all reviewers. UDC Article 3.3.3.7.a.
2. Ensure that the permit submittals match. Re-submit this permit once the above-mentioned DP is approved by all reviewers.

To re-submit, visit the Tucson Development Center Online at:
https://tdc-online.tucsonaz.gov/#/home

The instructions for resubmittal can be found at: Revisions and Resubmittals

Engineering Associate: Ryan Insalaco
ryan.insalaco@tucsonaz.gov
02/25/2026 Fire New Construction Standard REVIEW COMPLETED
02/03/2026 PDSD Application Completeness Express REVIEW COMPLETED