| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/09/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/09/2025 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | The current submittal is not an air balance report. Provide an air balancing report to verify that the HVAC systems, shown in the design drawings for TC-COM-0525-00955, are capable of supplying and exhausting at least the minimum ventilation and air flow rates called for in the design drawings. The balancing shall be performed by a qualified balancing contractor in accordance with the procedural standards of either the National Environmental Balancing Bureau (NEBB) or the Associated Air Balance Council (AABC). Reference: Section 403.3.1.5, IMC 2018 as amended by the City of Tucson. | ||
| 12/08/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |