Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0525-00955
Parcel: 14042023D

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0525-00955
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/09/2025 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT The current submittal is not an air balance report. Provide an air balancing report to verify that the HVAC systems, shown in the design drawings for TC-COM-0525-00955, are capable of supplying and exhausting at least the minimum ventilation and air flow rates called for in the design drawings. The balancing shall be performed by a qualified balancing contractor in accordance with the procedural standards of either the National Environmental Balancing Bureau (NEBB) or the Associated Air Balance Council (AABC). Reference: Section 403.3.1.5, IMC 2018 as amended by the City of Tucson.
12/08/2025 PDSD Application Completeness Express REVIEW COMPLETED