Permit Number: TC-COM-0525-00955
Parcel: 14042023D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0525-00955
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2025 Commercial Electrical Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 5/21/2025 5:15:27 PM
05/30/2025 Commercial Mechanical Standard APPROVED Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 5/28/2025 3:21:06 PM
06/05/2025 Water - PDSD Standard APPROVED
05/23/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting
06/10/2025 Site Engineering Standard NOT REQUIRED
06/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/30/2025 Commercial Building Standard REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 5/26/2025 5:24:29 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 5/19/2025 3:03:04 PM
1. General/Manufacturing Process: Please provide a detailed description of the manufacturing process. Provide
clarification on what is being manufactured and an overview of the process.
2. General/Storage Areas: It is unclear how the incoming goods area will be used. Please provide clarification on the
incoming goods area. What is being stored? Height of storage?
3. General/Locker Rooms: Enlarged locker room plans have not been provided. Provide enlarged views of the locker
rooms. Also, a provide a locker detail.
05/30/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 5/30/2025 10:15:41 AM
FIRST PLUMBING REVIEW:
1). Plan pages P1.2WH & P4.0WH: what will be drained into laboratory sink? Any harmful discharge will need to comply with
-2018 IPC 302 & 803
2). Plan Page P1.2WH: Missing shut off valve at lift pump. Add shut off valve at lift pump. -2018 IPC 712.2
06/05/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: Olga Salazar
PDSD Zoning Review Section

PROJECT: TC-COM-0525-00955– Manufacturing
Tenant Improvement (1st Review)
6950 S COUNTRY CLUB RD – I-1 Zoning

TRANSMITTAL DATE: June 5th, 2025

DUE DATE: June 5th, 2025

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans for compliance with the I-1 zone. The type of manufacturing was not specified. Add a note to the scope of work specifying the type of manufacturing that will occur on site in order to verify whether or not the proposed use will be in compliance with the use specific standards for the zone and use.


2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the proposed manufacturing use and compliance with the use specific standards.

3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified compliance with the use specific standards, the building plans can be approved by zoning.


If you have any questions about this transmittal, please contact zone1.desk@tucsonaz.gov.
05/21/2025 Fire New Construction Standard REVIEW COMPLETED Fire alarm and fire sprinkler upgrades requires a separate submittal and permit, fire extinguishers shall comply with Section 906 of the 2018IFC.
05/14/2025 PDSD Application Completeness Express REVIEW COMPLETED