Permit Number: TC-COM-0525-00942
Parcel: 141186590

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0525-00942
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2025 Commercial Building Standard APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 7/13/2025 10:10:30 PM

Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 7/14/2025 9:28:34 AM
07/15/2025 Outdoor Lighting Standard APPROVED
07/31/2025 Site Engineering Standard APPROVED
07/31/2025 Site Zoning Standard APPROVED
07/31/2025 Water - PDSD Standard APPROVED
07/31/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/18/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 7/17/2025 10:29:40 PM
First plumbing Review;
1). Plan Page A120: Missing secondary scupper locations, Add secondary scupper locations to roof layout Plan. -2018 IPC
1106.5, 1108
2). Plan Page A120: Missing scupper sizing calculations. Add scupper sizing calculations. -2018 IPC 1106.1, 1108.3
3). Plan Page P501: Missing detail showing Oxygen/Nitrogen room door labeling. Add detail showing Oxygen/Nitrogen room
door labeling.. -2018 NFPA99-5.1.3.1.8
07/10/2025 PDSD Application Completeness Express REVIEW COMPLETED