Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/15/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/15/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Provide complete electrical plans including; 1a. Show the location(s) on the electrical site plan of the breaker panel(s) utilized to provide power for the electric gates. 1b. Indicate the branch circuit number and panel on the electrical plan(s). 1c. Provide a complete panel schedule the correlates with the branch circuits assigned for the electric gates. Include load calculations. 1d. Provide power requirement specifications for the gate operators, perhaps manufacturers cut sheets or specifications. 1e. Indicate the routing of the branch circuits for the electric gates. Include conduit, conductors sizes and types, disconnecting means. Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
08/02/2024 | PDSD Application Completeness | REVIEW COMPLETED |