Permit Number: TC-COM-0524-00986
Parcel: 141153560

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0524-00986
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2024 Site Engineering NOT REQUIRED
06/04/2024 Site Zoning NOT REQUIRED
06/10/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/10/2024 Commercial Mechanical REQUIRES RESUBMIT Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.4, IECC 2018.
05/23/2024 PDSD Application Completeness REVIEW COMPLETED