Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - TC-COM-0524-00913
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/17/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
09/17/2024 | External Reviewers - Stantec | REQUIRES RESUBMIT | September 17, 2024 3rd Review Robert Caylor Construction Attn: Robert Caylor 2 E. Congress, Suite 900 Tucson, Arizona 85701 Re: THE TREASURY TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0524-00913 Stantec Project Number: 185215066 Stantec File Number: TUC-24-045 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms A-2 I-B N/A 499 Yes Yes Separate Permits: Automatic fire sprinklers, fire alarm, and kitchen hood suppression system. Deferred Submittals: None. Special Inspections: Epoxy and expansion anchors, structural steel, high-strength bolts, field welding. ARCHITECTURAL COMMENTS General 1. Addressed. 2. Addressed. 3. Addressed. 4. Addressed. 5. Addressed. Sheet A1 1. Addressed. 2. New Comment: The plans indicate the construction type as I-B and that the structural frame will not be modified. The structural plan-set indicates the floor assembly will be modified to accommodate proposed floor sinks. The removal of a portion of the structural concrete tees indicates the use of steel headers to reinforce the tee. Please provide a detail specifying the spray-applied fireproofing being used, thickness, ESR report number, etc. of the steel portion for this new structural frame to meet compliance with the 2-hour protection required for I-B construction. [Ref. IBC 2018 Sec. 601] 3. New Comment: Note on the cover of the drawings that special inspection is required for sprayed fire-resistant materials. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Sheet A6 1. Addressed. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS Sheet M4 1. Addressed.] Sheet M9 1. Addressed. PLUMBING COMMENTS Sheet P2 1. Addressed. Sheet P10 1. Addressed. 2. Addressed. ELECTRICAL COMMENTS Sheet E14 1. Addressed. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
09/12/2024 | PDSD Application Completeness | REVIEW COMPLETED |