Permit Number: TC-COM-0524-00913
Parcel: 11712087B

Address:
2 E CONGRESS ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-0524-00913
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
09/17/2024 External Reviewers - Stantec REQUIRES RESUBMIT September 17, 2024
3rd Review

Robert Caylor Construction
Attn: Robert Caylor
2 E. Congress, Suite 900
Tucson, Arizona 85701

Re: THE TREASURY
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0524-00913
Stantec Project Number: 185215066
Stantec File Number: TUC-24-045

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 I-B N/A 499 Yes Yes
Separate Permits: Automatic fire sprinklers, fire alarm, and kitchen hood suppression system.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, structural steel, high-strength bolts, field welding.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. Addressed.

3. Addressed.
4. Addressed.

5. Addressed.

Sheet A1

1. Addressed.

2. New Comment: The plans indicate the construction type as I-B and that the structural frame will not be modified. The structural plan-set indicates the floor assembly will be modified to accommodate proposed floor sinks. The removal of a portion of the structural concrete tees indicates the use of steel headers to reinforce the tee. Please provide a detail specifying the spray-applied fireproofing being used, thickness, ESR report number, etc. of the steel portion for this new structural frame to meet compliance with the 2-hour protection required for I-B construction. [Ref. IBC 2018 Sec. 601]

3. New Comment: Note on the cover of the drawings that special inspection is required for sprayed fire-resistant materials. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet A6

1. Addressed.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

Sheet M4

1. Addressed.]

Sheet M9

1. Addressed.

PLUMBING COMMENTS

Sheet P2

1. Addressed.

Sheet P10

1. Addressed.

2. Addressed.

ELECTRICAL COMMENTS

Sheet E14

1. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
09/12/2024 PDSD Application Completeness REVIEW COMPLETED