Permit Number: TC-COM-0524-00912
Parcel: 13213125A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0524-00912
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2024 Site Zoning APPROVED
06/03/2024 Water - PDSD APPROVED
05/30/2024 Site Engineering NOT REQUIRED
06/03/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/03/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised documents along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. Sheets A0.0B, A02A, A0.3A, A0.3B: Please replace CBC code references with 2018 IBC or 2009 ICC A117.1 IBC 107.2.1
2. Please amend the Project summary to include the 2018 International Existing Building Code. IBC 107.2.1
3. Please provide reference to the approved shell permit number on the plans per City of Tucson Commercial Submittal Requirements. (COTCSR) IBC 107.2.1 https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
4. Sheet A0.4: Please amend plans to show there is a demarcated, minimum 44-inch-wide aisle defined by full- or partial-height fixed walls or similar construction that will maintain the required width and lead directly from the retail area to the exit without obstructions. Alternatively, amend the plans to prevent occupants from the main retail area exiting through the stockroom. IBC 1016.2 exception #2.
5. Sheet A0.4: Please amend plans to provide a legend for the symbols S, M, L on the plan view. If it is seating, please identify the accessible spaces. IBC 107.2.1
6. Please amend plans to provide Copies of Energy Compliance Certificates (COMcheck) To include Envelope, Mechanical and Interior Lighting per (COTCSR) IBC 107.2.1

Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
06/03/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Verify complete compliance with the 2012 City of Tucson Outdoor Lighting Code (OLC) for the exterior lighting. Please see section 104 of the Outdoor Lighting Code and provide a site lighting plan with evidence that this parcel is in compliance as directed per this Code.

2 Please revise the IECC lighting calculations to the current 2018 IECC.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code.
06/03/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018.
2. The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation (e.g. for RTU-2, which serves two zones) is to be based on Table 403.3.1.1, IMC 2018 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3.1.1, IMC 2018
06/03/2024 Commercial Plumbing REQUIRES RESUBMIT Verify that the specified sensor faucet for the restroom lavatory has an automatic time-out so that it will operate for at least 10-seconds for accessibility and dispense a maximum of 0.25 gallons per metering cycle. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09
05/21/2024 Fire New Construction REVIEW COMPLETED
05/16/2024 PDSD Application Completeness REVIEW COMPLETED