Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0524-00912
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/21/2024 | Commercial Building | APPROVED | |||
06/20/2024 | Commercial Electrical | APPROVED | |||
06/24/2024 | Commercial Plumbing | APPROVED | |||
06/24/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/24/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Interlocking the operation of the restroom exhaust fan with the light switch will result in 100% of the supplied to the restroom being returned to the suite by way of the restroom door. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted during the hours of operation. [Initial comment: Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018.] | ||
06/07/2024 | PDSD Application Completeness | REVIEW COMPLETED |