Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0524-00906
Parcel: 14122004W

Address:
7655 S KOLB RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0524-00906
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2024 Commercial Electrical APPROVED
05/30/2024 Water - PDSD APPROVED
06/04/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/04/2024 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0524-00906
ADDRESS/PARCEL: (7655 S KOLB RD TUCSON, AZ 85756)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. Detail D1/A2.1 shows a Prefin Gravel Stop of 1 ½ inch tall on all roof edges. The Flat roof is sloping towards the center of the building shown on Drawing A3/A2.1 at ¼ inch per 12 inches. Wouldn’t this create ponding of 1 ½ inch deep before water goes over the edge? Please resolve this condition and submit a drawing that illustrates the solution.
2. Provide Fabric Shade Canopy drawings to include steel frame, steel columns, footing & shade. Provide the Shade Flame Spread Rating Index as well as the Fire Propagation Performance information.
3. EIFS: The drainage track shall be placed not less than 4 inches above the earth or 2 inches above paved areas and be of a type that will allow trapped water to drain to the exterior of the building. Per IBC 2512.1.2 Where porches, landings, garage aprons are located at same level as floor slab, provide concrete or CMU foundation curb or other approved means to achieve minimum 2 inch clearance between slab and drainage track.
4. Provide drawings illustrating the required ANSI A117.1 service counter height and width at the Reception Area, Soft Interview for both employees and visitors as well as designated stations within the Open Office area that are accessible complying to ANSI A117.1.
5. Please resubmit.
05/30/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Demonstrate energy code compliance for the building envelope using calculations based on the current code (i.e. COMcheck). Reference: Sections C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2018.
2. Show that rooftop units AC-1 and AC-2 meet the requirements of Section C403.5, IECC 2018 (economizers) unless exempted by compliance with the efficiency requirements of Table C403.5 (2), IECC 2018.
05/30/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Clarify the FFE for the building. The civil drawings show a FFE of 2808.25’ while P1.0 shows 2809.7’. Similarly, C400 shows the invert of the building sewer as 2802.25’ about five feet from the building while P1.0 shows an invert of 2805.2’ at the same location.
2. The maximum distance between cleanouts in the building sewer shall be 100-feet, measured along the developed pipe length from the upstream entrance of the cleanout. Reference: Section 708.1.1, IPC 2018.
3. Provide the dimensions of the rain gutter (detail B3/A2.1).
05/21/2024 Fire New Construction REQUIRES RESUBMIT -Sheet A0.2 states, in the code narrative, fire sprinklers and fire alarm will not be installed. Sheet A0.0 states fire sprinklers and fire alarm will be a deferred submittal. Conflicting information.
john.vincent@tucsonaz.gov
5203495581
05/28/2024 Site Engineering REQUIRES RESUBMIT The building permit can't be approved until the associated development package, TD-DEV-1023-00423, has been approved.

Lianne Evans
lianne.evans@tucsonaz.gov
05/28/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-COM-0524-00906 - TD-DEV-1023-00423
7655 S KOLB RD . – RH
TPD Eastside Annex (1st Review)

TRANSMITTAL DATE: May 28, 2024

Please resubmit revised drawings detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the RH zone (UDC 4.7.3). Protective Service (government owned and operated only)is a permitted use in this zone (Table 4.8-1).

1. Zoning has reviewed the building plans for compliance with development package TD-DEV-1023-00423 and although it appears that the building plans comply until DP is approved by all review agencies, Zoning cannot approve this building plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/14/2024 PDSD Application Completeness Express REVIEW COMPLETED