Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0524-00902
Parcel: 136130060

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0524-00902
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
07/05/2024 External Reviewers - SAFEBuilt APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 5/31/2024 12:28:52 AM




Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/27/2024 11:03:50 AM





Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 5/24/2024 6:16:13 PM




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 5/15/2024 11:38:05 AM
1. Comment for future information only: E0.6 EXTERIOR CUT SHEETS & IECC REPORTS: Tucson has specific exterior lighting calculations that should be performed according to City of Tucson/Pima County outdoor Lighting Code. However, Photometric report on Sheet E0.5 will be sufficient for this review when combined with the exterior lighting comcheck. Future submittals shall include required calculations.




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 7/2/2024 8:35:11 PM
Second Plumbing Review:OK
Resolved-1). Plan page A8.0 detail17: Detail 17 shows a single primary scupper discharging to a Downspout assembly that has the overflow installed beyond the structure. This doesn't correlate with plan page P1.3 Keynote #1 and doesn't comply
with 2018 IPC 1108.1 & 1108.2. Add a detail to plan page A8.0 correctly depicting a secondary overflow adjacent to the primary overflow. In accordance with -2018 IPC 1106.5 & section 1108
07/24/2024 Site Zoning APPROVED
07/31/2024 Bldg Permits - Post Review Express REVIEW COMPLETED
07/31/2024 Fire New Construction REVIEW COMPLETED
06/26/2024 PDSD Application Completeness Express REVIEW COMPLETED