Permit Number: TC-COM-0524-00902
Parcel: 136130060

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0524-00902
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2024 Site Engineering APPROVED
06/17/2024 Water - PDSD APPROVED
06/17/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/06/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 5/31/2024 12:28:52 AM


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 5/28/2024 3:13:11 PM
1. Sheet A8.4 / UL U419: UL fire resistant rated wall assemblies typically use proprietary materials as part of the testing process for the listing. Please provide the most recently published complete listed assembly for UL U411. The most recent version of this assembly, as published by UL is dated March 15, 2024. (2018 IBC Sec. 703.2) This would require that you cut and paste the entire most recently published UL listed assembly into the plan set.

2. Sheet A8.5 / UL U423: UL fire resistant rated wall assemblies typically use proprietary materials as part of the testing process for the listing. Please provide the most recently published complete listed assembly for UL U411. The most recent version of this assembly, as published by UL is dated February 16, 2024. (2018 IBC Sec. 703.2) This would require that you cut and paste the entire most recently published UL listed assembly into the plan set.

3. Sheet A1.2: The stair shafts are indicated as using the UL assembly U905, however that listed assembly has not been provided. Provide the listed assembly detail U905.



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 5/24/2024 6:16:13 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 5/15/2024 11:38:05 AM
1. Comment for future information only: E0.6 EXTERIOR CUT SHEETS & IECC REPORTS: Tucson has specific exterior lighting calculations that should be performed according to City of Tucson/Pima County outdoor Lighting Code. However, Photometric report on Sheet E0.5 will be sufficient for this review when combined with the exterior lighting comcheck. Future submittals shall include required calculations.


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 5/28/2024 10:31:48 PM
First Plumbing Review:
1). Plan page A8.0 detail17: Detail 17 shows a single primary scupper discharging to a Downspout assembly that has the overflow installed beyond the structure. This doesn't correlate with plan page P1.3 Keynote #1 and doesn't comply with 2018 IPC 1108.1 & 1108.2. Add a detail to plan page A8.0 correctly depicting a secondary overflow adjacent to the primary overflow. In accordance with -2018 IPC 1106.5 & section 1108
05/30/2024 Fire New Construction REQUIRES RESUBMIT -Provide two way communication system per IFC 1009.8 at elevator lobbies.
john.vincent@tucsonaz.gov
5203495581
06/06/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0524-00902 - TD-DEV-0323-00183
8750 E GOLF LINKS RD. - C-2
Personal Storage (1st Review)

TRANSMITTAL DATE: ‎June 6, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Personal Storage is a permitted use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.10.C.3 & .6.

1. COMMENT: Zoning has reviewed the building plan for compliance with TD-DEV-0323-00183, and although it appears that the plans match, Zoning cannot approve the building plans until the following comments have been addressed.

2. The sheet index lists the Civil Set. The development package sheets are to be provided in the building plan set they either need to be the stamped approved plans, marked for reference only, or removed from the building set. If you elect to mark for reference only do not mark the utility plans and if you elect to remove the plans leave the utility plans in the so Plumbing can review.

3. The accessible sign detail and bicycle rack detail do not match the approved details shown on the development package.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/14/2024 PDSD Application Completeness Express REVIEW COMPLETED