Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0524-00810
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/11/2024 | Commercial Mechanical | APPROVED | |||
06/11/2024 | Commercial Plumbing | APPROVED | |||
06/11/2024 | Water - PDSD | APPROVED | |||
06/12/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/06/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1.New electrical services require the utility feed to the service to be underground per 2018 IBC Amendment section 112.1.1. 2. Indicate fuse types for the service disconnects. Ref; 2019 IBC section 107.2.1 and adopted Amendments, 2017 NEC |
||
06/12/2024 | Commercial Structural | REQUIRES RESUBMIT | Please submit your revised documents along with a detailed response letter, which states how all Building Review Section comments were addressed. 1. Sheet G001: Please amend accessibility code to read - ANSI 117.1 -2009 as this is the currently enforced code in the City of Tucson. IBC 107.2.1 2. Sheet G001An architectural special inspections certificate for: impervious moisture barriers, EIFS. IBC 1705.1.1, 1705.14 – 1705.18,. Additionally, provide an architectural statement of special inspections, if required per the above items. IBC 1704.3 3. Sheet A501: Related to the above comment, please indicate a water resistive barrier, and indicate the type of barrier, as a water-resistive barrier coating would require a special inspection. IBC 1705.16.1 4. Sheet S1.0: Please amend plans to Identify all Special Inspection requirements. IBC 1705 Additionally, Please provide a Special Inspection Certificate with the next submittal. 5. Sheet S2.1: Please amend plans to ensure the Typical lintel schedule and the Ledger schedule are consistent and the same information is provided for both. IBC 107.2.7 For example, Page of the calcs indicated a 4x12 ledger and the schedule indicates a 3x12 ledger. The lintel schedule appears to be showing different framing members and jambs, than indicated in the calcs. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
06/05/2024 | Site Engineering | REQUIRES RESUBMIT | See zoning comment | ||
06/04/2024 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: TC-COM-0524-00810 2886 N 1ST AV. – C-2 Vehicle Rental & Sales & General Merchandise Sales (1st Review) TRANSMITTAL: June 4, 2024 This site is located in the C-2 zone (4.7.21). Vehicle Rental & Sales & General Merchandise Sales are allowed uses in the zone (UDC Table 4.8-4), subject to Use Specific Standard 4.9.9.G.1 & 2, & 4.9.9.B.1 1. As Development Package, TD-DEV-0524-00141, has not yet completed its 1st review Zoning cannot review the building plans for compliance with the DP. Zoning will review for compliance with the DP on the next submittal if the DP has completed the 1st review. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
05/26/2024 | Fire New Construction | REVIEW COMPLETED | |||
05/09/2024 | PDSD Application Completeness | REVIEW COMPLETED |