Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0523-01415
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Approved
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/20/2024 | External Reviewers - SAFEBuilt | APPROVED | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Approved Reason: Date Completed : 6/19/2024 11:40:46 AM Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 5/1/2024 1:57:22 PM Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Approved Reason: Date Completed : 5/2/2024 12:42:05 PM Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 5/1/2024 4:58:41 PM Comment only for E3 ELECTRICAL ONE-LINE DIAGRAM. Revised Transformer T1 size of 175 KVA is not a standard transformer size and will likely require a special order and longer lead time. It is also not listed in the transformer grounding detail. Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Approved Reason: Date Completed : 6/19/2024 9:05:17 PM Plumbing Plan Revision Review #1: OK Resolved-1). Plan page P0.1: The added #51A Chemical Dispenser needs an ASSE 1055 Backflow device. Update the plan page with a backflow device in accordance with -2018 IPC 608.14.8 |
||