Permit Number: TC-COM-0523-01415
Parcel: 124170410

Address:
825 S PARK AV

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0523-01415
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2024 External Reviewers - SAFEBuilt APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 6/19/2024 11:40:46 AM




Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/1/2024 1:57:22 PM




Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 5/2/2024 12:42:05 PM




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 5/1/2024 4:58:41 PM
Comment only for E3 ELECTRICAL ONE-LINE DIAGRAM. Revised Transformer T1 size of 175 KVA is not a standard
transformer size and will likely require a special order and longer lead time. It is also not listed in the transformer grounding
detail.





Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 6/19/2024 9:05:17 PM
Plumbing Plan Revision Review #1: OK
Resolved-1). Plan page P0.1: The added #51A Chemical Dispenser needs an ASSE 1055 Backflow device. Update the plan
page with a backflow device in accordance with -2018 IPC 608.14.8
06/20/2024 Bldg Permits - Post Review Express REVIEW COMPLETED
06/17/2024 PDSD Application Completeness Express REVIEW COMPLETED