Permit Number: TC-COM-0523-01387
Parcel: 10706113A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0523-01387
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2023 Water - PDSD APPROVED
06/27/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/05/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0523-01387

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/5/2023 4:27:28 PM
1. No structural work being completed. Approved.


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 6/5/2023 4:26:25 PM
1. General: Provide all manufacturer specification for the walk in coolers.
2. General: Provide clarification about the adjacent tenant and any required separations that may need to be required.
Are they considered separate buildings in accordance with 2018 IBC Section 503.1, or is it considered a nonseparated/separated mix use. Provide all clarification as to all applicable requirements of Sections 508.3 and 508.4.


Mechanical(M) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 6/5/2023 4:26:47 PM
1. Sheet M1: The structure shares a common wall with the adjoining structure. On the south wall of the building there are two outside air intakes. Ensure that these intakes meet the applicable separation requirements from other exhaust outlets in accordance with 2018 IMC Section 501.3.1.
2. Sheet M1: The bathroom exhaust appears that it may exhaust within 3' of an operable opening. Provide clarification that the exhaust meets the applicable separation requirements in accordance with 2018 IMC Section 501.3.1.


Electrical(E) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/5/2023 4:26:33 PM


Plumbing(P) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/5/2023 4:26:58 PM
06/13/2023 Site Engineering REQUIRES RESUBMIT See zoning comment
06/06/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0523-01387
2902 N El Burrito Av. I-1
Interior Remodel Botanical Warehouse (1st Review)

TRANSMITTAL DATE: ‎June 06, 2023

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in I-1 zone (UDC 4.7.29), Commercial Storage is an allowed use in the zone (UDC Table 4.8-5), subject to Use Specific Standards 4.9.10.A and 4.9.13.Q.
1. Clarify what the use is. If the proposed use is within the Retail Trade Use Group having anything to do with marijuana provide a copy of an approved Marijuana Use Authorization Letter with the next submittal.

2. Indicate clearly on the plans that the two sites are operating independently of each other on the next submittal.

If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov.
06/12/2023 Fire New Construction REVIEW COMPLETED
05/26/2023 PDSD Application Completeness Express REVIEW COMPLETED