Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0523-01284
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2023 Site Zoning APPROVED
06/01/2023 Site Engineering NOT REQUIRED
06/05/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/05/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0523-01284

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 6/3/2023 4:40:56 AM


Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 6/3/2023 4:39:49 AM
1. Please clarify, the Siemens documents are listed on TS1 as under separate cover however these were not included in the submittal. If there is work to be included in this permit, provide the documents.
2. Provide a life safety/ exit plan on the drawings for the first floor that indicates the travel distances as well as the occupant loads for the first floor in accordance with 2018 IBC 1004 and 1017.2. The door to the existing porch appears to be an exit for the existing passage corridor 101.
3. Indicate the required accessibility clearance for door 104 on the drawings. It is unknown if the new angled wall allows for a minimum of 48” clear on the latch side. ICC A117.1 figure 404.2.3.2.
4. Show the required 12” accessibility clearance for the second floor door to the patio. It appears that there may not be enough clearance on the latch side to the new HVAC wall enclosure. ICC A117.1 figure 404.2.3.2.
5. Clarify if there is an existing window in the control room that is being filled. If so, provide a detail or note for the work.



Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 6/3/2023 4:40:34 AM


Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 6/3/2023 4:40:20 AM
1. Indicate the location of the emergency lighting in the event of a power failure with battery backup to illuminate the egress path to exit door 104. 2018 IBC 1008.3.1. The exit signage shows this as an egress path from the existing passage corridor 101.
2. Indicate the location of an existing emergency light on the exterior at the exit doors to illuminate the landings or indicate new fixtures will be provided. 2018 IBC 1008.3.2 (5).



Plumbing(P) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 6/3/2023 4:40:44 AM
05/31/2023 Fire New Construction REVIEW COMPLETED
05/19/2023 PDSD Application Completeness REVIEW COMPLETED