Permit Number: TC-COM-0523-01265
Parcel: 12909146C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0523-01265
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
07/13/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0523-01265


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 6/1/2023 2:22:07 AM


Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 7/13/2023 1:41:13 AM
1. Provide a full set of drawings for approval, the resubmittal was missing three of the plumbing sheets.
2. Previous building comment 5: Provide ramp details and a section for the new ramp in circulation hall 105.
The detail does not show the required level landing at door 105. Indicate the size of the landing on the drawing. The landing shall include the 24" minimum clearance on the latch side of the door. ICC A117.1-2009 405.7.5, / figure 404.2.3.2.


Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 7/13/2023 1:15:34 AM



Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 7/13/2023 1:15:22 AM



Plumbing(P) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 7/13/2023 1:15:45 AM
07/06/2023 PDSD Application Completeness REVIEW COMPLETED