Permit Number: TC-COM-0523-01251
Parcel: 11005317A

Address:
3075 N SWAN RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0523-01251
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2023 Commercial Building APPROVED
05/26/2023 Site Engineering APPROVED
05/24/2023 Site Zoning APPROVED
06/16/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/16/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Show the location of the breaker panel feeding the under-canopy lighting and provide a panel schedule showing the lighting branch circuit including the panel identification. NEC 408.4

2 Verify that the DG Disconnect Switch is rated as suitable for use as service equipment. NEC 690.13C.

Ref; 2018 IBC section 107.2.1, 2017 NEC.
05/25/2023 Fire New Construction REVIEW COMPLETED
05/19/2023 PDSD Application Completeness Express REVIEW COMPLETED