Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0523-01251
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/15/2023 | Commercial Building | APPROVED | |||
| 05/26/2023 | Site Engineering | APPROVED | |||
| 05/24/2023 | Site Zoning | APPROVED | |||
| 06/16/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/16/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Show the location of the breaker panel feeding the under-canopy lighting and provide a panel schedule showing the lighting branch circuit including the panel identification. NEC 408.4 2 Verify that the DG Disconnect Switch is rated as suitable for use as service equipment. NEC 690.13C. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
| 05/25/2023 | Fire New Construction | REVIEW COMPLETED | |||
| 05/19/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |