Permit Number: TC-COM-0426-00560
Parcel: 13213104A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0426-00560
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2026 Commercial Building Standard APPROVED Building (B) Reviewer
Andrew Bevis; abevis@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 6/5/2026

Structural (S) Reviewer
Andrew Bevis; abevis@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 6/9/2026
06/09/2026 Commercial Electrical Standard APPROVED Electrical (E) Reviewer
Andrew Bevis; abevis@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 6/9/2026
06/09/2026 Commercial Plumbing Standard APPROVED Plumbing (P) Reviewer
Andrew Bevis; abevis@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 6/5/2026
06/24/2026 Site Engineering Standard APPROVED
06/24/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/09/2026 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical (M) Reviewer
Jorge Valido; jvalido@safebuilt.com
Discipline Status:Denied
Date Completed: 6/8/2026
1.(RESOLVED) - General -VAV 1-11 supply CFM at the Grills/diffusers id 950 CFM. VAV Schedule on Plan Sheet M5.1
states for VAV 1-11 Cooling 800 CFM Minimum 200 CFM. Confirm Supply air CFM for VAV 1-11. - 2024 IECC Section
C105.2Information on Construction Documents - 2024 IBC Section [A]107.2.1Information on Construction Documents.
◦VAV 1-11 Supply CFM 850. VAV Schedule on Plan Sheet M5.1 states for VAV 1-11 Cooling 800 CFM
Minimum 200 CFM. VAV 1-11 has a 50 CFM deficit.
2.(UNRESOLVED) - General -Tag/identify all Supply grills/diffusers for VAV2-08. - 2024 IECC Section
C105.2Information on Construction Documents - 2024 IBC Section [A]107.2.1Information on Construction Documents.
◦Comment not addressed. No correction made.
3.(RESOLVED) - General -VAV 2-13 on Plan Sheet M1.2 states "24x6 DL 600 CFM (TYP. 4 PL.)". It should state "24x6
DL 600 CFM (TYP. 5 PL.)". - 2024 IECC Section C105.2Information on Construction Documents - 2024 IBC Section
[A]107.2.1Information on Construction Documents.
◦Comment not addressed. Correction not made.
4.(UNRESOLVED) - General -Provide an Air Balance Schedule for the first-floor Welding Lab area. - 2024 IECC
Section C408.2.2 System Adjusting and Balancing.
◦Should have read "Provide an Air Balance Schedule for the first-floor Welding Lab area". Welding Lab has
30000 CFM Exhaust system with 28 hood systems. Supply air to welding lab is VAV 1-01 and VAV 1-02 which
equals 5500 CFM of supply air. There is also a 44x20 Return air duct from PAC-1 (4900 CFM). Where is the
Makeup air coming from? - 2024 IECC Section C408.2.2 System Adjusting and Balancing.
06/22/2026 Fire New Construction Standard REVIEW COMPLETED
06/04/2026 PDSD Application Completeness Express REVIEW COMPLETED